E-mail Conguration – EMAILCFG
Name Status Default Unit Displayed text* Description
senderP1 - Sender E-mail Part1 Sender e-mail, identier part
@ @
senderP2 - Sender E-mail Part2 Sender e-mail, domain part
recip1P1 - Recip1 E-mail Part1 Recipient 1,identier part
@ @
recip1P2 - Recip1 E-mail Part2 Recipient 1,domain part
recip2P1 - Recip2 E-mail Part1 Recipient 2,identier part
@ @
recip2P2 - Recip2 E-mail Part2 Recipient 2,domain part
smtpP1 0 to 255 0 - SMTP IP Addr Part 1 SMTP IP address part 1
smtpP2 0 to 255 0 - SMTP IP Addr Part 2 SMTP IP address part 2
smtpP3 0 to 255 0 - SMTP IP Addr Part 3 SMTP IP address part 3
smtpP4 0 to 255 0 - SMTP IP Addr Part 4 SMTP IP address part 4
accP1 - Account E-mail Part1 Account e-mail, identier part
@ @
accP2 - Account E-mail Part2 Account e-mail, domain part
accPass - Account Password Account password
portNbr 0 to 255 25 - Port Number Port number
srvTim 0 to 255 30 sec Server Timeout Server timeout
srvAut 0 to 1 0 - Server Authentication
*Depends on the selected language (English by default).
NOTE: If you need to add an option, please contact your local
carrier Service provider.
ModbusRTU Cong. – MODBUSRS
Name Status Default Unit Displayed text* Description
modrt_en no/yes 0 - RTU Server Enable RTU Server Enable
ser_UID 1 to 247 1 - Server UID Server UID
metric no/yes 1 - Metric Unit Metric Unit
swap_b 0 to 1 0 - Swap Bytes Swap Bytes
0 = Big Endian 0 = Big Endian
1 = Little Endian 1 = Little Endian
baudrate 9600 to 38400 9600 - Baudrate Baudrate
0 = 9600 0 = 9600
1 = 19200 1 = 19200
2 = 38400 2 = 38400
parity 0 to 2 0 - Parity Parity
0 = No parity 0 = No parity
1 = Odd parity 1 = Odd parity
2 = Even parity 2 = Even parity
stop_bit 0 to 1 0 - Stop bit number Stop bit number
0 = One stop bit 0 = One stop bit
1 = Two stop bit 1 = Two stop bit
real_typ 0 to 1 0 - Real Type Management Real Type Management
0 = Float X10 0 = Float X10
1 = IEE 754 1 = IEE 754
reg32bit 0 to 1 1 - Enable 32 bits registers Enable 32 bits registers
0 = IR/HR in 16 bit mode 0 = IR/HR in 16 bit mode
1 = IR/HR in 32 bit mode 1 = IR/HR in 32 bit mode
*Depends on the selected language (English by default).