JBus 
code
Code Alarm description Reset type Action taken Possible cause
60 10033 COOLER PUMP #2 FAULT Manual As above As above
61 10034 CIRCUIT A RECLAIM OPERATION 
FAILURE  
Not applicable - -
62 10035 CIRCUIT B RECLAIM OPERATION 
FAILURE  
Not applicable - -
63 10037 CIRCUIT A - REPEATED HIGH DISCHARGE 
GAS OVERRIDES 
Automatic (no discharge 
gas override within 30 
min) or Manual (the 
counter forced to 0)
None Repetitive capacity 
decreases
64 10038 CIRCUIT B - REPEATED HIGH 
DISCHARGE GAS OVERRIDES 
As above None As above
65 10040 CIRCUIT A - REPEATED LOW SUCTION 
TEMP OVERRIDES
Manual 
(the counter forced to 0)
Circuit A shuts down Repetitive capacity 
decreases
66 10041 CIRCUIT B - REPEATED LOW SUCTION 
TEMP OVERRIDES
As above Circuit B shuts down As above
67 10043 LOW ENTERING WATER TEMPERATURE 
IN HEATING
Automatic (EWT returns 
to normal or Heating 
mode is disabled)
None Low entering uid 
temperature in 
Heating mode
68 10051 WATER EXCHANGER FLOW SWITCH  
FAILURE                              
Manual Unit shuts down Flow switch fault
69 10052 HEAT RECLAIM FLOW SWITCH  FAILURE   Not applicable - -
70 10063 CIRCUIT A HIGH PRESSURE SWITCH 
FAILURE 
Manual Circuit A shuts down Switch fault
71 10064 CIRCUIT B HIGH PRESSURE SWITCH 
FAILURE 
Manual Circuit B shuts down As above
72 10090 WATER EXCHANGER FLOW SWITCH 
SETPOINT CONFIGURATION FAILURE
Manual Unit cannot be started Defective or 
incorrectly wired ow 
controller
73 10091 CIRCUIT A FREE COOLING VALVE 
INCOHERENT POSITION 
Manual Circuit A shuts down The valve has not 
reached the expected 
position in the 
assigned time 
74 10092 CIRCUIT B FREE COOLING VALVE 
INCOHERENT POSITION 
Manual Circuit B shuts down As above
75 10094 CIRCUIT A FREE COOLING OPERATION 
FAILURE  
Automatic Free cooling cycle stopped. Unit 
returns to mechanical cooling
The refrigerant pump 
has not started 
correctly or it has 
cavitated
76 10095 CIRCUIT B FREE COOLING OPERATION 
FAILURE  
Automatic As above As above
77 10097 WATER EXCHANGER TEMPERATURE 
SENSORS SWAPPED
Manual Unit shuts down Input and output 
temperature reversed
78 10099 REFRIGERANT LEAKAGE DETECTION Automatic None Refrigerant leak or 
leak detector 
defective
79 10101 DC FREE COOLING PROCESS FAILURE Automatic None Fan fault, dirty beam
88 10210 CIRCUIT A LOW DELTA PRESSURE 
OPERATION FAILURE 
Manual Circuit A shuts down Circuit running in part 
load with all available 
compressors and low 
delta pressure during 
operation. Not enough 
capacity available / 
failed or disabled due 
to compressor(s)
89 10211 CIRCUIT B LOW DELTA PRESSURE 
OPERATION FAILURE
Manual Circuit B shuts down As above
80 11202 WATER LOOP: DELTA PRESSURE ERROR Automatic, if water 
pressure delta returns to 
normal
Unit shuts down Too low or high water 
pressure reading
81 11203 WATER LOOP: PRESSURE TOO LOW Automatic, if water 
pressure reading returns 
to normal and the alarm 
occurred not more than 6 
times in the last 24 hours 
(otherwise manual)
Unit shuts down Low pump inlet 
pressure is below 
60 kPa
82 11204 WATER LOOP: PUMP NOT STARTED Automatic Pump is stopped Too low or high water 
pressure reading
84 11206 WATER LOOP: PUMP OVERLOAD Automatic None Water loop pressure 
drop too low
85 11207 WATER LOOP: FLOW TOO LOW Automatic, when water 
ow reading returns to 
normal
Pump is stopped Water loop pressure 
drop too high 
8 - DIAGNOSTICS
52