6- STANDARD  CONTROL OPERATIONS AND  OPTIONS
   
 
6.1 
External thermostat control 
 
 
In appropriate cases the unit may be controlled by an 
external thermostat approved by Carrier. This function 
requires the use of a thermostat with volt-free contacts 
(contacts without potential), as well as a specific 
configuration of the SmartVu control. The function is only 
active when operating type Thermostat (TSTAT) is selected 
in the GENCONF menu. 
 
In this operating type, the thermostat controls the 
following functions: 
•
  Stopping/starting the internal fan 
•
  Determining the space temperature control point, 
•
  Selecting heating/cooling 
•
  Controlling compressor capacity, gas or electric 
•
  Controlling the economizer (fully open position or 
minimum closed position only). 
 
The SmartVu system continues to control the following 
functions: 
•
  Defrosting related to the heat pumps 
•
  Head pressure control 
•
  Power exhaust control 
•
  Minimum stop/start times on the compressors 
•
  Unit diagnostics. 
 
 
The following functions are disabled: 
•
  Humidification 
•
  Controlling a hot-water system 
•
  Timer programming 
•
  Purge. 
 
The description of the thermostat outputs, based on the 
unit type, is given in the chapter 3.6 - “Connections at the 
user terminal block”. 
 
6.2 
Cooling only unit 
 
 
•
  Contact G open: The internal fan is stopped and the 
economizer is closed. 
•
  Contact G closed: The internal fan is activated and the 
•
  economizer is opened to its minimum position. 
•
  Contact Y1 closed and Y2 open: If the unit is fitted with 
an economizer, it is opened to its maximum position, if 
•
  external conditions permit (see chapter 5.16 - 
“Economizer”). 
•
  Otherwise the economizer is set to its minimumposition 
and the first compressor is started up. If the unit has no 
economizer, the first compressor is started up. 
Contacts Y1 and Y2 closed: The economizer is held fully 
open if external conditions are still acceptable. A compressor 
is started up. If external conditions nolonger permit the 
economizer to be used, it is set to itsminimum position and 
the second compressor is started up. If the outdoor 
temperature is lower than 15°C, thecompressors will not be 
authorised to start up and onlythe economizer will be used. If 
the unit has no economizer, the second compressor is 
started up. 
 
 
 
 
 
 
•
  Contact W1 closed and W2 open: The first gas or 
electric stage is started. 
•
  Contacts W1 and W2 closed: The second gas or 
electric stage is started. 
 
 
6.3 
Single-circuit heat pump unit 
 
•
  Contact G open: The internal fan is stopped and the 
economizer is closed. 
•
  Contact G closed: The internal fan is activated and the 
economizer is opened to its minimum position. 
•
  Contact O closed and Y closed: If the unit is fitted with 
an economizer, it is modulated to maintain the minimum 
supply air temperature setpoint at +2.8°C, if external 
conditions permit (see chapter 5.16 - “Economizer”). 
Otherwise the economizer is set to its minimum position 
and the compressor is started up in cooling mode. If 
the unit has no economizer, the compressor is started 
up in cooling mode. 
•
  Contacts O open and Y closed: If the unit is fitted with an 
economizer, it is set to its minimum position and 
the first compressor is started up in heating mode. 
•
  Contact W1 closed and W2 open: The first gas or electric 
stage is started. 
•
  Contacts W1 and W2 closed: The second gas or 
electric stage is started. 
 
6.4 
Dual-circuit/dual-compressor heat pump unit 
 
 
•
  Contact G open: The internal fan is stopped and the 
economizer is closed. 
•
  Contact G closed: The internal fan is activated and the 
economizer is opened to its minimum position. 
•
  Contact O closed, Y1 closed and Y2 open: If the unit is 
fitted with an economizer, it is opened to its maximum 
position, if external conditions permit (see chapter 5.16 - 
“Economizer”). Otherwise the economizer is set to its 
minimum position and the first compressor is started up 
in cooling mode. If the unit has no economizer, the first 
compressor is started up in cooling mode. 
•
  Contacts O, Y1 and Y2 closed: The economizer is held 
fully open , if external conditions are still acceptable. A 
compressor is started up in cooling mode. If external 
conditions no longer permit the economizer to be used, it 
is set to its minimum position and the second 
compressor is started up in cooling mode. If the outdoor 
temperature is lower than 15°C, the compressors will not 
be authorised to start up and only the economizer will be 
used. If the unit has no economizer, the second 
compressor is started up in cooling mode. 
•
  Contact O open, Y1 closed and Y2 open: If the unit is 
fitted with an economizer, it is set to its minimum 
position and the first compressor is started up in heating 
mode. If the unit has no economizer, the first 
compressor is started up in heating mode. 
•
  Contact O open, Y1 and Y2 closed: The economizer is 
held in its minimum position. The second compressor is 
started up in heating mode. 
•
  Contact W1 closed: The first gas or electric stage is 
started. 
NOTE: All compressor anti-short cycles remain 
activated