6.5  - Unit start/stop control
 
The unit  state  is determined  based  on a number  of factors, 
including its operating type, active overrides, open contacts, , or 
alarms triggered due to operating conditions. 
The  table  given  below  summarises  the  unit  control  type 
[ctrl_typ]  and  its  running  status  with  regard  to  the  following 
parameters:
 
■ 
Operating type: 
This operating type is selected using the Start/ 
Stop button on the user interface.
 
IMPO
RTANT: When the unit is stopping or there is a demand to 
stop the unit, compressors are stopped consecutively.
 
In case of emergency stop, all compressors are stopped at 
the same time
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
.
Start/stop  force  command  [ROOF_S_S]: 
Rooftop 
start/stop force command can be used to control the unit state 
in the Network mode.
 
-
 
Command set to stop: The unit is halted.
 
-
 
Command set to start: The unit runs in accordance with 
schedule 1.
 
■ 
Remote start/stop contact status [Onoff_sw]: 
Start/stop 
contact status can be used to  control the  unit  state in the 
Remote operating type.
 
■ 
G: 
This contact is used when unit is in thermostat
 
operating type 
■ 
Start/stop  schedule [roof_occ]: 
Occupied or unoccupied 
status of the unit.
 
■ 
Network emergency stop command [EMSTOP]: 
If activated, 
the unit shuts down regardless of the active operating type.
 
■ 
General alarm: 
The unit shuts down due to failure.