6.6  - 
Calculating the space temperature 
 
Up to two sensors (one of which is optional) may be used to 
calculate the space temperature. Depending on the 
configuration (see see GENCONF menu), space temperature is 
either calculated as the average of all readings, or is taken 
from the minimum or maximum reading. 
6.7  - 
Space temperature control point 
 
 
Depending on the current operating type, the active setpoint 
can be selected: 
•
  By choosing the item in the GENUNIT menu 
•
  Via the user’s volt-free contacts 
•
  Via network commands 
•
  Via the setpoint timer program (schedule 2). 
•
  The following tables summarise the possible selections 
•
  depending on the control types (local, remote or network) 
•
  and the following parameters: 
•
  Setpoint select in local control: item LSP_SEL in the 
•
  GENUNIT menu permits selection of the active setpoint, 
•
  if the unit is in local operating type. 
•
  Heating/cooling operating mode. 
•
  Setpoint selection contacts: Setpoint selection contact 
•
  status. 
•
  Schedule 2 status: Schedule for setpoint selection 
 
 LOCAL OPERATING MODE 
 
6.8  - Offset
 
 
 
An offset means that the active space temperature setpoint 
is altered in line with external parameters. This may be 
carried out in one of the following ways: 
•
  By the user with the aid of an adjustment slider located on 
the main T-56 space temperature sensor (optional). The 
offset range is ± 3 K in increments of 1 K. 
•
  By the user with the aid of buttons located on the T-59 space 
temperature sensor (optional). 
The offset range is ± 3 K in increments of 0.5 K. 
•
  Automatically in cooling mode, by reference to the outdoor 
temperature (if the function has been validated 
in the HCCONFIG menu). In this case, the function is 
generally used to limit the difference between the 
indoor and outdoor temperatures in order to prevent thermal 
shock. 
IMPORTANT: It is not possible to use both types of offset 
at the same time. If the offset from the T-56 or T-59 sensor 
is non-zero, offset based on the outdoor temperature 
isignored. 
6.9  – Smart Start
 
 
This mode permits heating or cooling the room before it is 
occupied so that the space temperature has reached its 
setpoint at the beginning of the occupied period. The control 
calculates an anticipated start-up value in minutes, based 
on a user configurable factor (anticipated start-up factor 
expessed in minutes/degrees that must be adjusted for the 
installation) and the difference between the setpoint and 
 
 
 
the space temperature. The higher the anticipated start-up 
factor or the higher the setpoint difference, the earlier the 
change-over to occupied mode is anticipated. However, the 
start-up cannot be anticipated by more than 60 minutes. 
 
6.10 –
Heating/cooling mode 
 
 
Units with heat pumps or additional heating stages may 
operate in either heating or cooling mode. 
 
• Cooling mode is active when: 
Space temperature is above: occ_cool (occupied 
mode) or uno_cool (unoccupied mode) 
• Heating mode is active when: 
Space temperature is below: occ_heat (occupied 
mode) or uno_heat (unoccupied mode) 
• Units remains in ventilation mode (without cooling or 
heating) when the space temperature is between occ_ 
heat and occ_cool (occupied mode) or uno_heat and 
uno_cool (unoccupied mode). 
 
6.11 - 
Heat Cool changeover 
 
Cooling/Heating changeover can be forced through 
SmartVu or CCN. The machine will be forced to do only 
heating or cooling upon the changeover parameter. When 
the unit is forced to heating but it needs to do cooling 
based on sensor, the unit will switch to standby. Same in 
reverse case. 
 
6.12 - 
Frost protection mode 
 
 
The unit may be configured to be in frost protection mode 
when in unoccupied mode (GENCONF menu). In this case 
the fan is shut down and is only authorised to restart if the 
space temperature falls below the frost protection setpoint. 
It shuts down again when space temperature is 1.5 K above 
the frost protection setpoint. Selecting frost protection does 
not affect how the unit operates in occupied mode. The 
frost protection mode for unoccupied periods has to be 
selected in the GENCONF menu.