CONFIGURATION
SELECTIONS DESCRIPTION
HIGH SPEED DELAY
1MIN
0TO10MINUTES
IN 0.5 MINUTE IN-
CREMENTS
Select the length of time unit remains in low speed
before transitioning to high speed.
SATELLITE COMM
(Optional)
(NOT SUPPORTED IN VECTOR
MT)
This feature is not supported for Vector MultiTemp
models at this time.
UNIT OPERATION:
STANDARD
RAIL
STANDARD = The microprocessor is set to control
trailer refrigeration operation.
RAIL = Not recommended for Vector MT
ENABLE INTELLISET AT = KEY
NO
YES
YES = Allows access to the Intelliset menu using
the = key.
NO = Allows access to the Intelliset menu using the
SELECT key.
SUPPLY AIR LIMIT FOR S/S
10.4°FTO+32°F
(--12°Cto+0°C)
(in 0.5°For°Cin-
crements)
DEFAULT: 21.2°F
(--6°C)
Coldest allowable supply air temperature for
Compartment 1 when unit is running in Start/Stop.
SUPPLY AIR LIMIT FOR CONT
10.4°FTO+32°F
(--12°Cto+0°C)
(in 0.5°For°Cin-
crements)
DEFAULT: 23°F
(--5°C)
Coldest allowable supply air temperature for
Compartment 1 when unit is running in Continuous.
SAT2 (Optional and available for 2
Compartment Units)
NOT INSTALLED
(0)
INSTALLED (1)
NOT INSTALLED-- Supply Air Temperature Sensor
is not installed in Compartment 2 evaporator.
INSTALLED -- Supply Air Temperature Sensor is
installed in Compartment 2 evaporator.
C2 SUPPLY AIR LIMIT FOR S/S
10.4°FTO+32°F
(--12°Cto+0°C)
(in 0.5°For°Cin-
crements)
DEFAULT: 26.6°F
(--3°C)
Coldest allowable supply air temperature for
Compartment 2 when unit is running in Start/Stop.
C2 SUPPLY AIR LIMIT FOR CONT
10.4°FTO+32°F
(--12°Cto+0°C)
(in 0.5°For°Cin-
crements)
DEFAULT: 30.2°F
(--1°C)
Coldest allowable supply air temperature for
Compartment 2 when unit is running in Continuous.
HIGH SPEED PULLDOWN
ON / OFF When active, this logic indicates if temperature lim-
its regulating the exit of pulldown mode are modi-
fied or not.
ON = Allows for high speed cool pulldown when
only one compartment is configured.
OFF = Normal unit operation.