62-11039 5-10
CONFIGURATION
SELECTIONS DESCRIPTION
DOOR SWITCH UNIT SHUT-
DOWN:
(Optional)
NOT AVAILABLE FOR 3
COMPARTMENT UNITS
ALARM ONLY
UNIT SHUTDOWN
LOW ENGINE
SPEED
DATA RECORDER
ONLY
ALARM ONLY = When Door Switch indicates that
the door is open, a warning alarm will be displayed
in the MessageCenter.
UNIT SHUTDOWN = When Door Switch indicates
that the door is open, a warning alarm will be dis-
played in the MessageCenter, and the unit will shut-
down.
LOW ENGINE SPEED = When Door Switch indi-
cates that the door is open, the engine will be
forced to low speed.
DATA RECORDER ONLY = The data recorder will
record every time the door is opened or closed.
There will be no alarms or messages displayed in
the MessageCenter.
SET TIME The following will allow the Real Time Clock in the
Data Recorder to be set. The time set here can be
read in the unit data list.
• MONTH 1--12 Select the correct month of the year.
•DAY 1--31 Select the correct day of the month.
•YEAR 1998 -- 2037 Select the correct year.
•HOURS 0--23 Select the correct hour (0--11 is AM / 12--23 is PM)
•MINUTES 0--59 Select the correct minute.
PERISHABLE FAN MODE
ON / OFF If perishable setpoint is in a specified range and this
mode is enabled, the fan will be set off.
FROZEN PRIORITY COOLING
Refer to Section 4.4.3
ON /OFF ON = Coolant capacity priority will be to the
compartments with setpoints in the frozen range.
OFF = Normal unit operation.
FROZEN PRIORITY TIMER
5MIN
5--60 MINUTES IN
1 MINUTE INCRE-
MENTS
Defines the number of minutes spent in Frozen
Priority Cooling when enabled.
PERISH PRIORITY TIMER
5MIN
5--60 MINUTES IN
1 MINUTE INCRE-
MENTS
Defines the number of minutes spent in Perishable
Priority Cooling when Frozen Priority Cooling is en-
abled.
PERISH PRIORITY TEMP
OFF
3.6°Fto27°F
(2°Cto 15°C) (in
0.5° Cor°Fincre-
ments
Allowable number of degrees from setpoint that box
temperature can change before overriding frozen
priority cooling mode and entering normal unit op-
eration.
COMPARTMENT
CONFIGURATION
(NDP33GN6HBV2)
2
1thru4
COMPARTMENT
CONFIGURATION
(NDP33GN6HBV3)
6
5thru16
e
ect correct system
rom
a
e2-2
8 HR ADDITIONAL DATA:
YES / NO YES = When the RS is turned OFF, the data re-
corder will continue to record data for an additional
8 hours.
NO = When the RS is turned OFF, the data record-
er will stop recording data.
CONDENSER PRESS CONTROL
STD
-- 5
+5
The recommended setting for this is STD. This
setting should not be changed unless discussed
with a Carrier Transicold Factory Service engineer
or Field service engineer.