62-110393-23
3.16 FUNCTIONAL CHANGE (PARAMETERS)
COOL DEFROST ALARM START-STOP
SETPOINT BOX TEMPERATURE
ALARM LIST
SELECT
MANUAL
DEFROST
HEAT CONTINUOUS
+36 F
-20
START--STOP/
CONTINUOUS
2
1. Press the SELECT key until the MessageCenter displays
“PRESS ↑↓ TO VIEW SETTINGS”.
2. By pressing the UP ARROW key, you will move through the
Function List beginning at the top or by pressing the DOWN
ARROW key, you will move through the Function List beginning
at the bottom.
3. To change one of the Functions, bring the Function you wish to change into the MessageCenter,
and press the = key. ↑↓TO SCROLL, THEN = TO SAVE” will show in the MessageCenter.
Pressing either UP or DOWN ARROW key will begin to change the
Function setting. The MessageCenter will flash, indicating that a change has been made that
has not been entered into memory.
4. Continue pressing UP or DOWN ARROW key until the desired value is showing, then press
the = key. The MessageCenter will stop flashing. The new value is now in memory.
If the = key is not pressed within 10 seconds, the MessageCenter will change to
“FUNCTION NOT CHANGED”. This will appear for 5 seconds, then return to the last
Functional Parameter shown. If no further keys are pressed, the default message will be
displayed another 10 seconds.
PRESS ↑↓TO VIEW SETTINGS
NOTE
Any Function that is shown with a padlock sym-
bol cannot be changed from the keypad.