 APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — RUN STATUS (cont)
MODE — SERVICE TEST
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS PAGE NO.
HRS COMPRESSOR RUN HOURS
HR.A1 Compressor A1 Run Hours 0 to 999999 HRS HR_A1 config 101
HR.A2 Compressor A2 Run Hours 0 to 999999 HRS HR_A2 config 101
HR.B1 Compressor B1 Run Hours 0 to 999999 HRS HR_B1 config 101
HR.B2 Compressor B2 Run Hours 0 to 999999 HRS HR_B2 config 101
STRT COMPRESSOR STARTS
ST.A1 Compressor A1 Starts 0 to 999999 CY_A1 config 101
ST.A2 Compressor A2 Starts 0 to 999999 CY_A2 config 101
ST.B1 Compressor B1 Starts 0 to 999999 CY_B1 config 101
ST.B2 Compressor B2 Starts 0 to 999999 CY_B2 config 101
TMGD TIMEGUARDS
TG.A1 Compressor A1 Timeguard CMPA1_TG 101
TG.A2 Compressor A2 Timeguard CMPA2_TG 101
TG.B1 Compressor B1 Timeguard CMPB1_TG 101
TG.B2 Compressor B2 Timeguard CMPB2_TG 101
TG.H1 Heat Relay 1 Timeguard HS1_TG 101
TG.H2 Heat Relay 2 Timeguard HS2_TG 101
TG.H3 Heat Relay 3 Timeguard HS3_TG 101
TG.H4 Heat Relay 4 Timeguard HS4_TG 101
TG.H5 Heat Relay 5 Timeguard HS5_TG 101
TG.H6 Heat Relay 6 Timeguard HS6_TG 101
VERS SOFTWARE VERSION NUMBERS
MBB CESR131343-xx-xx string 101
ECB1 CESR131249-xx-xx string 101
ECB2 CESR131465-xx-xx string 101
SCB1 CESR131226-xx-xx string 101
CEM CESR131174-xx-xx string 101
SCB2 CESR131226-xx-xx string 101
RXB CESR131465-xx-xx string 101
EXV CESR131172-xx-xx string 101
VFD
MARQ CESR131171-xx-xx string 101
NAVI CESR130227-xx-xx string 101
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS PAGE NO.
TEST Service Test Mode ON/OFF MAN_CTRL
STOP Local Machine Disable YES/NO UNITSTOP config 23,28
S.STP Soft Stop Request YES/NO SOFTSTOP forcible 23
FAN.F Supply Fan Request YES/NO SFANFORC forcible 23
F.4.CH 4 in. Filter Change Mode YES/NO FILT4CHG 23
INDP TEST INDEPENDENT OUTPUTS
ECN.C Economizer Act.Cmd.Pos. ECONCTST 23
E.PWR Economizer Power Test ECONPTST 23
E.CAL Calibrate the Economizer? ECON_CAL 23,110
PE.A Power Exhaust Relay A PE_A_TST 23
PE.B Power Exhaust Relay B PE_B_TST 23
PE.C Power Exhaust Relay C PE_C_TST 23
H.I.R Heat Interlock Relay ON/OFF HIR_TST 23
ALRM Remote Alarm/Aux Relay ON/OFF ALRM_TST 23
FANS TEST FANS
S.FAN Supply Fan Relay ON/OFF SFAN_TST 23
S.VFD Supply Fan VFD Speed 0 to 100 % SGVFDTST 23
CD.F.A Condenser Fan Circuit A ON/OFF CNDA_TST 23
CD.F.B Condenser Fan Circuit B ON/OFF CNDB_TST 23
A.VFD MtrMaster A Commanded % 0 to 100 % OAVFDTST 23
B.VFD MtrMaster B Commanded % 0 to 100 % OBVFDTST 23
MM.F.A MotorMastr Fan Circuit A ON/OFF MM_A_TST 23
MM.F.B MotorMastr Fan Circuit B ON/OFF MM_B_TST 23
OV.A Outdoor Fan VFD A Control Cmd %          0 to 100  %  OV_A_TST 23
OV.B Outdoor Fan VFD B Control Cmd % OV_B_TST 23
COOL TEST COOLING
A1 Compressor A1 Relay ON/OFF CMPA1TST 23
A2 Compressor A2 Relay ON/OFF CMPA2TST 23
MLV Min. Load Valve (HGBP) ON/OFF MLV_TST 23
DS.CP Digital Scroll Capacity 20 to 100 % DSCAPTST 23
B1 Compressor B1 Relay ON/OFF CMPB1TST 23
B2 Compressor B2 Relay ON/OFF CMPB2TST 23
RHV HumidiMiZer 3-Way Valve  ON/OFF RHVH_TST  23,25
C.EXV Condenser EXV Position  0 to 100 % CEXVHTST  23,25
B.EXV Bypass EXV Position 0 to 100 % BEXVHTST 23,25
HEAT TEST HEATING
HT.ST Requested Heat Stage 0 to MAX HTST_TST 23
HT.1 Heat Relay 1 ON/OFF HS1_TST 23
HT.2 Heat Relay 2 ON/OFF HS2_TST 23
HT.3 Relay 3 W1 Gas Valve 2 ON/OFF HS3_TST 23
HT.4 Relay 4 W2 Gas Valve 2 ON/OFF HS4_TST 23
HT.5 Relay 5 W1 Gas Valve 3 ON/OFF HS5_TST 23
HT.6 Relay 6 W2 Gas Valve 3 ON/OFF HS6_TST 23