223
CONTROLS SETPOINT AND CONFIGURATION LOG
MODEL NUMBER: Software Version
SERIAL NUMBER: MBB CESR131343--
DATE: RCB CESR131249--
TECHNICIAN: ECB CESR131465-
NAVI CESR131227--
SCB CESR131226--
CEM CESR131174--
MARQ CESR131171--
ITEM EXPANSION RANGE DEFAULT ENTRY
UNIT UNIT CONFIGURATION
C.TYP Machine Control Type 1 to 6 (multi-text strings) 4
CV.FN Fan Mode (0=Auto, 1=Cont) 0 to 1 (multi-text strings) 1
RM.CF Remote Switch Config 0 to 3 (multi-text strings) 0
CEM CEM Module Installed Yes/No No
TCS.C Temp.Cmp.Strt.Cool Factr 0 to 60 min 0
TCS.H Temp.Cmp.Strt.Heat Factr 0 to 60 min 0
SFS.S Fan Fail Shuts Down Unit Yes/No No
SFS.M Fan Stat Monitoring Type 0 to 2 (multi-text strings) 0
VAV.S VAV Unocc.Fan Retry Time 0 to 720 min 50
SIZE Unit Size (20-60) 20 to 60 20
DP.XR Disch.Press. Transducers Yes/No No
SP.XR Suct. Pres. Trans. Type 0 to 1 (multi-text strings) 0
RFG.T Refrig: 0=R22 1=R410A 0 to 1 (multi-text strings) 1
CND.T Cnd HX Typ:0=RTPF 1=MCHX 0 to 1 (multi-text strings) 0
MAT.S MAT Calc Config 0 to 2 (multi-text strings) 1
MAT.R Reset MAT Table Entries? Yes/No No
MAT.D MAT Outside Air Default 0 to 100% 20
ALTI Altitude……..in feet: 0 to 60000 0
DLAY Startup Delay Time 0 to 900 sec 0
STAT TSTAT_Both Heat and Cool Yes/No No
AUX.R Auxiliary Relay Config 0 to 3 0
SENS INPUT SENSOR CONFIG
SPT.S Space Temp Sensor Enable/Disable Disable
SP.O.S Space Temp Offset Sensor Enable/Disable Disable
SP.O.R Space Temp Offset Range 1 to 10 5
RRH.S Return Air RH Sensor Enable/Disable Disable
FLT.S Filter Stat.Sw.Enabled ? Enable/Disable Disable
COOL COOLING CONFIGURATION
Z.GN Capacity Threshold Adjst –10 to 10 1
MC.LO Compressor Lockout Temp –20 to 55 dF 40
C.FOD Fan-off Delay, Mech Cool 0 to 600 sec 60
MLV Min. Load Valve? (HGBP) Yes/No No
DS.EN Enable Digital Scroll? Yes/No No
DS.MC DS Min Digital Capacity 25 to 100% 50
DS.AP Dig Scroll Adjust Delta 0 to 100% 100
DS.AD Dig Scroll Adjust Delay 15 to 60 sec 20
DS.RP Dig Scroll Reduce Delta 0 to 100% 6
DS.RD Dig Scroll Reduce Delay 15 to 60 sec 30
DS.RO Dig Scroll Reduction OAT 70 to 120 dF 95
DS.MO Dig Scroll Max Only OAT 70 to 120 dF 105
HPSP Head Pressure Setpoint 80 to 150 dF 100
LASP Low Ambient Setpoint 70 to 150 100
M.M. Motor Master Control? Yes/No No
MM.OF Motor Master Setpoint Offset –20 to 20 –10
MM.RR Motor Master PD Run Rate 10 to 120 10
MM.PG Motor Master Proportional Gain 0.0 to 5 1
MM.DG Motor Master Derivative Gain 0 to 5 0.3
MM.TI
Motor Master Integration Time 0 to 50 30