UNIT START-UP CHECKLIST
MODEL NO.: _________________________________ SERIAL NO.: _____________________________________
SOFTWARE VERSION _________________________ TECHNICIAN: ____________________________________
DATE: _______________________________________
PRE-START-UP:
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
REMOVE ALL COMPRESSOR SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTRUCTIONS
VERIFY INSTALLATION OF ECONOMIZER HOOD PER INSTRUCTIONS
(including relocation of OAT sensor if necessary)
VERIFY INSTALLATION OF ALL OPTIONS AND ACCESSORIES
VERIFY PROPER INSTALLATION AND LOCATION OF STATIC PRESSURE TRANSDUCERS
(Supply Duct and Building Pressure when applicable)
VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT
VERIFY INSTALLATION AND LOCATION OF LAT SENSORS (multi-staged gas, SCR electric, hydronic heat only)
CHECK GAS PIPING FOR LEAKS (48A ONLY)
CHECK THAT RETURN-AIR FILTER AND OUTDOOR-AIR FILTERS ARE CLEAN AND IN PLACE
VERIFY THAT UNIT IS LEVEL WITHIN TOLERANCES FOR PROPER CONDENSATE DRAINAGE
CHECK FAN WHEELS AND PROPELLERS FOR LOCATION IN HOUSING/ORIFICE, AND SETSCREW IS TIGHT
VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED
VERIFY THAT SUCTION, DISCHARGE, AND LIQUID SERVICE VALVES ON EACH CIRCUIT ARE OPEN
VERIFY THAT CRANKCASE HEATERS HAVE BEEN ON 24 HOURS BEFORE START-UP
START-UP:
ELECTRICAL
SUPPLY VOLTAGE L1-L2 __________ L2-L3 _________ L3-L1 __________
COMPRESSOR AMPS — COMPRESSOR NO. 1 L1 _________ L2 ___________ L3 _________
COMPRESSOR AMPS — COMPRESSOR NO. 2 L1 _________ L2 ___________ L3 _________
SUPPLY FANS AMPS (CV/SAV) ________ EXHAUST FAN AMPS ___________
(VAV) _________ *
*VAV fan supply amps reading must be taken with a true RMS meter for accurate readings.
TEMPERATURES
OUTDOOR-AIR TEMPERATURE _________ F DB (Dry Bulb)
RETURN-AIR TEMPERATURE _________ F DB _________ F WB (Wet Bulb)
COOLING SUPPLY AIR _________ F
GAS HEAT SUPPLY AIR _________ F (48A ONLY)
ELECTRIC HEAT SUPPLY AIR _________ F (50A ONLY, IF EQUIPPED)
NOTE: To avoid injury to personnel and damage to equipment or
property when completing the procedures listed in this start-up
checklist, use good judgment, follow safe practices, and adhere
to the safety considerations/information as outlined in preced-
ing sections of this Controls, Start-Up, Operation, Service, and
Troubleshooting document.