Building Pressure Control
The building pressure control sequence provides control of pres-
sure in the building through the modulating flow rate function of
the modulating power exhaust option. This function also provides
control of the constant volume 2-stage power exhaust option.
BUILDING PRESSURE CONFIGURATION
The building pressure configurations are found at the local dis-
play under Configuration

BP. See Table 65.
Building Pressure Config (BP.CF)
This configuration selects the type of building pressure control.
BP.CF = 0, No building pressure control
BP.CF = 1, constant volume two-stage power exhaust
based on economizer position
BP.CF = 2, multiple stage building pressure control based
on a building pressure sensor
BP.CF = 3, VFD building pressure control based on a
building pressure sensor
Building Pressure PID Run Rate (BP.RT)
This configuration selects the run time of the PID algorithm.
This configuration is only active when BP.CF = 3. It is recom-
mended that this value not be changed without guidance from
Service Engineering.
Building Pressure Proportional Gain (BP.P)
This configuration selects the proportional gain of the PID al-
gorithm. This configuration is only active when BP.CF = 3. It
is recommended that this value not be changed without guid-
ance from Service Engineering.
Building Pressure Integral Gain (BP.I)
This configuration selects the integral gain of the PID algo-
rithm. This configuration is only active when BP.CF = 3. It is
recommended that this value not be changed without guidance
from Service Engineering.
Building Pressure Derivative Gain (BP.D)
This configuration selects the derivative gain of the PID algo-
rithm. This configuration is only active when BP.CF = 3. It is
recommended that this value not be changed without guidance
from Service Engineering.
Building Pressure Setpoint Offset (BP.SO)
This configuration is the value below the building pressure set-
point to which the building pressure must fall in order to turn
off power exhaust control. This configuration is only active
when BP.CF = 3.
Building Pressure Minimum Speed (BP.MN)
This configuration is the minimum allowed VFD speed during
building pressure control. This configuration is only active
when BP.CF = 3.
Building Pressure Maximum Speed (BP.MX)
This configuration is the maximum allowed VFD speed during
building pressure control. This configuration is only active
when BP.CF = 3.
VFD Fire Speed (BP.FS)
This configuration is the VFD speed override when the control
is in the purge or evacuation smoke control modes. This con-
figuration is only active when BP.CF = 3.
Power Exhaust Motors (BP.MT)
This configuration is machine dependent and instructs the
building pressure control algorithm whether the unit has 4 or 6
motors to control. The motors are controlled by three power
exhaust relays A, B, and C. These relay outputs are located at
the local display under Outputs

FANS

PE.A,B,C.
The following table illustrates the number of motors each relay
is in control of based on BP.MT:
Building Pressure Sensor (BP.S)
This configuration allows the reading of a building pressure
sensor when enabled. This is automatically enabled when
BP.CF = 2 or 3.
Building Pressure (+/–) Range (BP.R)
This configuration establishes the range in in. wg that a 4 to
20 mA sensor will be scaled to. The control only allows sen-
sors that measure both positive and negative pressure.
Table 65 — Building Pressure Configuration
*Some configurations are machine dependent.
BP.MT PE_A Relay PE_B Relay PE_C Relay
1 (4 motors) 1 Motor 2 Motors 1 Motor
2 (6 motors) 1 Motor 2 Motors 3 Motors
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT
BP BUILDING PRESS. CONFIG
BP.CF Building Press. Config 0 to 3 BLDG_CFG 0*

BP.RT Bldg.Pres.PID Run Rate 5 to 120 sec BPIDRATE 10

BP.P Bldg. Press. Prop. Gain 0 to 5 BLDGP_PG 0.5

BP.I Bldg.Press.Integ.Gain 0 to 2 BLDGP_IG 0.5

BP.D Bldg.Press.Deriv.Gain 0 to 5 BLDGP_DG 0.3

BP.SO BP Setpoint Offset 0.0 to 0.5 " H2O BPSO 0.05

BP.MN BP VFD Minimum Speed 0 to 100 % BLDGPMIN 10

BP.MX BP VFD Maximum Speed 0 to 100 % BLDGPMAX 100

BP.FS VFD/Act. Fire Speed/Pos. 0 to 100 % BLDGPFSO 100
BP.MT Power Exhaust Motors 1 to 2 PWRM 1*
BP.S Building Pressure Sensor Enable/Dsable BPSENS Dsable*
BP.R Bldg Press (+/–) Range 0 to 1.00 " H2O BP_RANGE 0.25
BP.SP Building Pressure Setp. -0.25 -> 0.25 " H2O BPSP 0.05
BP.P1 Power Exhaust On Setp.1 0 to 100 % PES1 35
BP.P2 Power Exhaust On Setp.2 0 to 100 % PES2 75
B.CFG BP ALGORITHM CONFIGS
BP.SL Modulating PE Alg. Slct. 1 to 3 BPSELECT 1
BP.TM BP PID Evaluation Time 0 to 10 min BPPERIOD 1
BP.ZG BP Threshold Adjustment 0.1 to 10.0 " H2O BPZ_GAIN 1
BP.HP High BP Level 0 to 1.000 " H2O BPHPLVL 0.05
BP.LP Low BP Level 0 to 1.000 " H2O BPLPLVL 0.04