APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES (cont)
TABLE NAME RANGE UNITS POINT NAME DEFAULT
GSCONFIG
Unit Size 20-60 tons UNITSIZE
Cnd HX Typ: 0=RTPF 1=MCHX COILTYPE
Machine Control Type CTRLTYPE
Enable Digital Scroll? No/Yes DIGCMPEN
Dehumidification Config DHSELECT
Outdoor VFD Enable No/Yes OV_ENA
Outdoor VFD PI Run Rate 5-120 secs OV_RATE
Outdoor VFD Prop. Gain 0-5 OV_PG
Outdoor VFD Integ. Time 0.5 - 200 secs OV_TI
Outdoor VFD Anti-Windup 0.1 - 1 OV_AU
Outdoor VFD SCT DeadBand 0 - 20 degF OV_SCTDB
Outdoor VFD Dehum-RH SPD 0-100 % OV_RH
OV MinStartSpeed Low Amb 0-100 % OV_STMIN
OV Prop. Gain at Low Amb 0 - 5 OV_PG_LA
OV Intg. Time at Low Amb 0.5 - 200 secs OV_TI_LA
Outdoor VFD MvgAvgFltrPt OV_MAFP
T24_CFG
Economizer Installed ? Yes/No ECON_ENA Yes
SAT Settling Time secs SAT_SET 240
MBB Sensor Heat Relocate Yes/No HTLATMON No
Log Title 24 Faults Yes/No T24LOGFL No
T24 Econ Move Detect T24ECMDB 1
T24 Econ Move SAT Test T24ECSTS 10
T24 Econ Move SAT Change T24SATMD 0.2
T24 Econ RAT-OAT Diff T24RATDF 15
T24 Heat/Cool End Delay T24CHDLY 25
T24 Test Minimum Pos. T24TSTMN 15
T24 Test Maximum Pos. T24TSTMX 85
SP__
Static Pres.VFD Control? No STATICFG No
Constant Vol IDF is VFD? Yes/No CVIDFVFD No
Static Pres.Fan Control? Yes STATPFAN Yes
Static Pressure Sensor Enable/Disable SPSENS Disable
Static Press. Low Range –10 to 0 SP_LOW 0
Static Press. High Range 0 to 10 SP_HIGH 5
Static Pressure Setpoint 0 to 5 " H2O SPSP 1.5
VFD Minimum Speed 10 to 50 % STATPMIN 20
VFD Maximum Speed 50 to 100 % STATPMAX 100
VFD Fire Speed Override 0 to 100 % STATPFSO 100
VFD Heating Min Speed 75 to 100 % VFDHTMIN 75
Stat. Pres. Reset Config 0 to 4 (multi-text strings) SPRSTCFG 0
SP Reset Ratio (" /dF) 0 to 2.00 SPRRATIO 0.2
SP Reset Limit in iwc(" ) 0 to 2.00 SPRLIMIT 0.75
SP Reset Econo.Position 0 to 100 % ECONOSPR 5
Stat.Pres.PID Run Rate 1 to 200 sec SPIDRATE 2
Static Press. Prop. Gain 0 to 100 STATP_PG 20
Static Pressure Intg. Gain 0 to 50 STATP_IG 2
Static Pressure Derv. Gain 0 to 50 STATP_DG 0
Static Press.System Gain 0 to 50 STATP_SG 1
TRIM
Air Temp Lvg SF Trim –10 to 10 ^F SAT_TRIM 0
RAT Trim –10 to 10 ^F RAT_TRIM 0
OAT Trim –10 to 10 ^F OAT_TRIM 0
SPT Trim –10 to 10 ^F SPT_TRIM 0
Cir A Sat.Cond.Temp Trim –30 to 30 ^F SCTATRIM 0
Cir B Sat.Cond.Temp Trim –30 to 30 ^F SCTBTRIM 0
Suct.Press.Circ.A Trim –50 to 50 PSI SPA_TRIM 0
Suct.Press.Circ.B Trim –50 to 50 PSI SPB_TRIM 0
Dis.Press.Circ.A Trim –50 to 50 PSI DPA_TRIM 0
Dis.Press.Circ.B Trim –50 to 50 PSI DPB_TRIM 0
Static Press. Trim (ma) –2 to 2 SPMATRIM 0
Bldg. Pressure Trim (ma) –2 to 2 BPMATRIM 0
SWLG
Filter Status Inpt-Clean Open/Close FLTSLOGC Open
IGC Feedback - Off Open/Close GASFANLG Open
RemSw Off-Unoc-Strt-NoOv Open/Close RMTINLOG Open
Economizer Switch - No Open/Close ECOSWLOG Open
Fan Status Sw. - Off Open/Close SFSLOGIC Open
Dmd.Lmt.Sw.1 - Off Open/Close DMD_SW1L Open
Dmd.Lmt.-Dehumid - Off Open/Close DMD_SW2L Open
IAQ Disc.Input - Low Open/Close IAQINLOG Open
Fire Shutdown - Off Open/Close FSDLOGIC Open
Press. Switch - Off Open/Close PRESLOGC Open
Evacuation Sw. - Off Open/Close EVACLOGC Open
Smoke Purge Sw. - Off Open/Close PURGLOGC Open