APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
COMPRESR
Compressor A1 Relay On/Off CMPA1
Compressor A1 Feedback On/Off CSB_A1
Curr.Sens.Brd. A1 Status ascii CSBA1ASC
CSB A1 Feedback Alarm Enable/Disable CSB_A1EN config
Comp A1 Locked Out ? Yes/No CMPA1LOK
Compressor A1 Strikes CMPA1STR
Enable Compressor A1 Enable/Disable CMPA1ENA config
Compressor A2 Relay On/Off CMPA2
Compressor A2 Feedback On/Off CSB_A2
Curr.Sens.Brd. A2 Status ascii CSBA2ASC
CSB A2 Feedback Alarm Enable/Disable CSB_A2EN config
Comp A2 Locked Out ? Yes/No CMPA2LOK
Compressor A2 Strikes CMPA2STR
Enable Compressor A2 Enable/Disable CMPA2ENA config
Compressor B1 Relay On/Off CMPB1
Compressor B1 Feedback On/Off CSB_B1
Curr.Sens.Brd. B1 Status ascii CSBB1ASC
CSB B1 Feedback Alarm Enable/Disable CSB_B1EN config
Comp B1 Locked Out ? Yes/No CMPB1LOK
Compressor B1 Strikes CMPB1STR
Enable Compressor B1 Enable/Disable CMPB1ENA config
Compressor B2 Relay On/Off CMPB2
Compressor B2 Feedback On/Off CSB_B2
Curr.Sens.Brd. B2 Status ascii CSBB2ASC
CSB B2 Feedback Alarm Enable/Disable CSB_B2EN config
Comp B2 Locked Out ? Yes/No CMPB2LOK
Compressor B2 Strikes CMPB2STR
Enable Compressor B2 Enable/Disable CMPB2ENA config
Digital Scroll Capacity 20 to 100 CMPDSCAP
DMANDLIM
Active Demand Limit 0 to 100 % DEM_LIM forcible
Percent Total Capacity 0 to 100 % CAPTOTAL
Demand Limit Select 0 to 3 DMD_CTRL config
Demand Limit Switch 1 On/Off DMD_SW1 forcible
Demand Limit Switch 2 On/Off DMD_SW2 forcible
Demand Limit Sw.1 Setpt. 0 to 100 % DLSWSP1 config
Demand Limit Sw.2 Setpt. 0 to 100 % DLSWSP2 config
4-20 ma Demand Signal 4 to 20 ma DMDLMTMA forcible
Demand Limit at 20 ma 0 to 100 % DMT20MA config
CCN Loadshed Signal 0 to 99 DL_STAT
Loadshed Group Number 0 to 99 SHED_NUM config
Loadshed Demand Delta 0 to 60 % SHED_DEL config
Maximum Loadshed Time 0 to 120 min SHED_TIM config
ECON_MIN
Econo Damper Command Pos % ECONOCMD forcible
Econo Damper Current Pos % ECONOPOS
Econo Current Min. Pos. % MIN_POS
Diff.Air Quality in PPM DAQ
Econo Position Override ECOORIDE forcible
IAQ Min.Pos.Override % IAQMINOV forcible
Econ Remote 10K Pot Val. ECON_POT forcible
IAQ - PPM Return CO2 IAQ forcible
OAQ - PPM Return CO2 OAQ forcible
IAQ - Discrete Input IAQIN forcible
IAQ Demand Vent Min.Pos. % IAQMINP config
Economizer Min.Position % ECONOMIN config
IAQ Analog Sensor Config IAQANCFG config
IAQ 4-20 ma Fan Config IAQANFAN config
IAQ Discrete Input Confg IAQINCFG config
IAQ Disc.In. Fan Config IAQINFAN config
IAQ Econo Override Pos. % IAQOVPOS config
Diff.Air Quality LoLimit DAQ_LOW config
Diff.Air Quality HiLimit DAQ_HIGH config
DAQ PPM Fan Off Setpoint DAQFNOFF config
DAQ PPM Fan On Setpoint DAQFNON config
Diff. AQ Responsiveness IAQREACT config
IAQ Low ReferenceIAQREFLconfig
IAQ High Reference IAQREFH config
OAQ Lockout Value OAQLOCK config
OAQ 4-20ma Sensor Config ma OAQANCFG config
IAQ milliamps ma IAQ_MA
OAQ milliamps OAQ_MA
Calculated Econ Minimum % CALCECMN
Econ Pos at Min VFD Spd % EPOSMNFS
Econ Pos at Max VFD Spd % EPOSMXFS