195
LEGEND
USER DEFINED BINARY 18 R/W
"0=OFF
1=ON"
user_binary_18_1 BV:2928
USER DEFINED BINARY 19 R/W
"0=OFF
1=ON"
user_binary_19_1 BV:2929
USER DEFINED BINARY 20 R/W
"0=OFF
1=ON"
user_binary_20_1 BV:2930
ELEMENT COMMUNICATIONS ALARM R
"0=COMM NORMAL
1=COMM LOST"
comm_lost_alm_1 BV:15
CIR B SUCTION PRESSURE Rpsig suction_press_b_1 AV:1604
USE LINKAGE R/W
"0=NO
1=YES"
use_linkage_1 BV:2605
EQUIPMENT TOUCH RESET LINKAGE ALARM R/W
"0=NO
1=YES"
et_reset_as_link_1 BV:5123
SYSTEM SPACE TEMPERATURE R°F system_spt_1 AV:1902
SYSTEM SPACE RH R%rh system_rh_1 AV:1904
SYSTEM SPACE AQ Rppm system_aq_1 AV:1903
MAXIMUM DAMPER POSITION R/W % 0 to 100 max_dmpr_pos_1 AV:3052
MINIMUM DAMPER POSITION R/W % 0 to 100 min_dmpr_pos_1 AV:3053
MAXIMUM RESET R/W inH2O max_reset_1 AV:3054
CONTROLLING STATIC PRESSURE SETPOINT R inH2O ct_sa_static_stpt_1 AV:3055
STATIC PRESSURE RESET ENABLE R/W
"0 = DISABLE
1 = ENABLE"
st_pr_rst_en_1 BV:3051
APPENDIX E — UPC OPEN CONTROLLER (cont)
NETWORK POINTS LIST (CONT)
NAME READ/WRITE UNITS RANGE OBJECT NAME OBJECT ID
BP — Building Pressure
CEM — Controls Expansion Module
DAQ — Differential Air Quality
DBC — Dry Bulb Changeover
DCV — Demand Controlled Ventilation
DDBC — Differential Dry Bulb Changeover
DEC — Differential Enthalpy Changeover
DH — Dehumidification
EDT — Evaporator Discharge Temperature
IAQ — Indoor Air Quality
IGC — Integrated Gas Control
LAT — Leaving Air Temperature
n/a — Not Available
OAEC — Outdoor Air Enthalpy Changeover
OAQ — Outdoor Air Quality
OAT — Outdoor Air Temperature
PID — Proportional, Integral, Derivative
R—Read
RAT — Return Air Temperature
RH — Relative Humidity
SASP — Supply Air Setpoint
SP — Setpoint
SPT — Space Temperature
TSTAT — Thermostat
VAV — Variable Air Volume
VFD — Variable Frequency Drive
W—Write