EasyManua.ls Logo

Carrier WEATHERMAKER 48A2020 - Page 195

Carrier WEATHERMAKER 48A2020
230 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
195
LEGEND
USER DEFINED BINARY 18 R/W
"0=OFF
1=ON"
user_binary_18_1 BV:2928
USER DEFINED BINARY 19 R/W
"0=OFF
1=ON"
user_binary_19_1 BV:2929
USER DEFINED BINARY 20 R/W
"0=OFF
1=ON"
user_binary_20_1 BV:2930
ELEMENT COMMUNICATIONS ALARM R
"0=COMM NORMAL
1=COMM LOST"
comm_lost_alm_1 BV:15
CIR B SUCTION PRESSURE Rpsig suction_press_b_1 AV:1604
USE LINKAGE R/W
"0=NO
1=YES"
use_linkage_1 BV:2605
EQUIPMENT TOUCH RESET LINKAGE ALARM R/W
"0=NO
1=YES"
et_reset_as_link_1 BV:5123
SYSTEM SPACE TEMPERATURE F system_spt_1 AV:1902
SYSTEM SPACE RH R%rh system_rh_1 AV:1904
SYSTEM SPACE AQ Rppm system_aq_1 AV:1903
MAXIMUM DAMPER POSITION R/W % 0 to 100 max_dmpr_pos_1 AV:3052
MINIMUM DAMPER POSITION R/W % 0 to 100 min_dmpr_pos_1 AV:3053
MAXIMUM RESET R/W inH2O max_reset_1 AV:3054
CONTROLLING STATIC PRESSURE SETPOINT R inH2O ct_sa_static_stpt_1 AV:3055
STATIC PRESSURE RESET ENABLE R/W
"0 = DISABLE
1 = ENABLE"
st_pr_rst_en_1 BV:3051
APPENDIX E — UPC OPEN CONTROLLER (cont)
NETWORK POINTS LIST (CONT)
NAME READ/WRITE UNITS RANGE OBJECT NAME OBJECT ID
BP Building Pressure
CEM Controls Expansion Module
DAQ Differential Air Quality
DBC Dry Bulb Changeover
DCV Demand Controlled Ventilation
DDBC Differential Dry Bulb Changeover
DEC Differential Enthalpy Changeover
DH Dehumidification
EDT Evaporator Discharge Temperature
IAQ Indoor Air Quality
IGC Integrated Gas Control
LAT Leaving Air Temperature
n/a Not Available
OAEC Outdoor Air Enthalpy Changeover
OAQ Outdoor Air Quality
OAT Outdoor Air Temperature
PID Proportional, Integral, Derivative
R—Read
RAT Return Air Temperature
RH Relative Humidity
SASP Supply Air Setpoint
SP Setpoint
SPT Space Temperature
TSTAT Thermostat
VAV Variable Air Volume
VFD Variable Frequency Drive
W—Write