 APPENDIX F — OPTIONAL FACTORY-INSTALLED LOW AMBIENT MOTORMASTER
®
 V CONTROL (cont)
Table M — Program Parameters for the Operating Mode
LEGEND
PARAMETERS DESCRIPTION MODE 1 MODE 2 MODE 4
P01 Line Voltage: 01 = low line, 02 = high line 1 2 2
P02 Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz 1 1 1
P03 Startup mode: flying restart 6 6 6
P04 Stop mode: coast to stop 111
P05 Standard Speed source: 01 = keypad, 04 = 4 to 20mA (NO PI), 05 = R22 or R410A, 06 = R134a 4 4 4
P06 TB-14 output: 01 = none 111
P08 TB-30 output: 01 = none 111
P09 TB-31 Output: 01 = none 111
P10 TB-13A function sel: 01 = none 1 1 1
P11 TB-13B function sel: 01 = none 1 1 1
P12 TB-13C function sel: 01 = none 1 1 1
P13 TB-15 output: 01 = none 111
P14 Control: 01 = Terminal strip 1 1 1
P15 Serial link: 02 = enabled 9600,8,N,2 with timer 2 2 2
P16 Units editing: 02 = whole units 2 2 2
P17 Rotation: 01 = forward only, 03 = reverse only 1 1 1
P19 Acceleration time: 20 sec 20 20 20
P20 Deceleration time: 10 sec 10 10 10
P21 DC brake time: 0 000
P22 DC BRAKE VOLTAGE 0% 0 0 0
P23 Min freq = 8 Hz ~ 100 – 160 rpm 8 8 8
P24 Max freq 60 60 50
P25 Current limit: (%) 125 110 110
P26 Motor overload: 100 100 100 100
P27 Base freq: 60 or 50 Hz 60 60 50
P28 Fixed boost: 0.5% at low frequencies 0.5 0.5 0.5
P29 Accel boost: 0% 000
P30 Slip compensation: 0% 000
P31 Preset spd #1: speed if loss of control signal 57 57 47
P32 Preset spd #2: 0 000
P33 Preset spd #3: 0 000
P34 Preset spd 4 default — R22 and R410A setpoints. TB12-2 open 24 24 24
P35 Preset spd 5 default — R134a setpoint. TB12-2 closed 12.6 12.6 12.6
P36 Preset spd 6 default 000
P37 Preset spd 7 default 000
P38 Skip bandwidth 000
P39 Speed scaling 000
P40 Frequency scaling 50 or 60 Hz 60 60 50
P41 Load scaling: default (not used so NA) 200 200 200
P42
Accel/decel #2: default (not used so NA) 60 60 60
P43 Serial address 111
P44 Password:111 111 111 111
P45 Speed at min signal: 8 Hz; used when PID mode is disabled and 4 to 20 mA input is at 4 mA 8 8 8
P46 Speed at max feedback: 60 or 50 Hz. Used when PID disabled and 4 to 20 mA input is at 20 mA 60 60 50
P47 Clear history? 01 = maintain. (set to 02 to clear) 1 1 1
P48 Program selection: Program 1 – 12 1 2 4
P61 PI Mode: 05 = reverse, 0 to 5V, 01 = no PID 5 5 5
P62 Min feedback = 0 (0V *10) 000
P63 Max feedback = 50 (5V * 10) 50 50 50
P64 Proportional gain = 3.5% 3.5 3.5 3.5
P65 Integral gain = .2 0.2 0.2 0.2
P66 PI accel/decel (setpoint change filter) = 10 10 10 10
P67 Min alarm 000
P68 Max alarm 000
NA — Not Applicable
PI — Proportional Integral
PID — Proportional Integral Derivative