CD Automation srl CD3000E-3PH from 25A to 500A User’s Manual
42
12.3.2 External Current Profiler (Terminals 9 and 7)
The secondary input is for the External Current Profiler or for the External Feed-Back. The secondary
input is already configured in line with customer requirements that are defined in the Order Code. The
Order Code is written on the identification label.
However, if you wish to change the secondary input proceed as follows:
Caution: this procedure must be performed only by qualified persons
Size S09 Size S11/S13/S14
JP3
C
B
A
Type (0÷10Vdc)
P070  P090 
Jumper
Current Profiler 0÷2 0 A-B
External Feed-Back 3 1 B-C
JP20
C
B
A
External Current Profiler or External Feed-Back Input calibration procedure
When you change the hardware setting is necessary make the Input calibration procedure.
To make the Input calibration procedure follow these steps:
Give the power supply.
With Control Panel go in the Hardware menu (P000  = 5)
Set the input signal to the min value (ex. 0V for 0÷10V)
Set the parameter P061  = 1
Press ENTER key
Set the input signal to the max value (ex.10V for 0÷10V 5V for 0÷5V)
Set the parameter P062  = 1
Press ENTER key
The Input calibration procedure is done.