CD Automation srl CD3000E-3PH from 25A to 500A User’s Manual
54
14.2 Hardware Menu
P057 (H39)

Calibration min value of analog input 1 R/W
Function:
This parameter saves in memory the min value of the primary analog input
(see par. 12.3.1)
Value: 0 = Default
1 = Save value
Note: The input Calibration procedure is necessary only if you change the input type
(ex. from 0÷10V to 4÷20mA) and must be performed only by qualified persons.
P058 (H3A)

Calibration max value of analog input 1 R/W
Function:
This parameter saves in memory the max value of the primary analog input
(see par. 12.3.1)
Value: 0 = Default
1 = Save value
Note: The input Calibration procedure is necessary only if you change the input type
(ex. from 0÷10V to 4÷20mA) and must be performed only by qualified persons.
P061 (H3D)

Calibration min value of analog input 2 R/W
Function:
This parameter saves in memory the min value of the External Current Profiler
analog input (see par. 12.3.2)
Value: 0 = Default
1 = Save value
Default: 0
Note: The input Calibration procedure is necessary only if you change the input type
(ex. from 0÷10V to 0÷5V) and must be performed only by qualified persons.
P062 (H3E)

Calibration max value of analog input 2 R/W
Function:
This parameter saves in memory the max value of the External Current Profiler
analog input (see par. 12.3.2)
Value: 0 = Default
1 = Save value
Default: 0
Note: The input Calibration procedure is necessary only if you change the input type
(ex. from 0÷10V to 0÷5V) and must be performed only by qualified persons.
P097 (H61)

Offset of the Analog Outputs R/W
Function: This parameter is used to set the offset for the Analog Outputs.
Value: 0 = 0 ÷ 10Vdc / 0 ÷ 20mA
1 = 4 ÷ 20mA
Default: 0 (if not specified in the Order Code)
P103 (H67)

Digital input configuration (terminal 20) R/W
Function: This parameter selects the function of digital input.
Value: 0 = Additional Reset Alarm
1 = Setpoint Zero
2 = Feed-back Selection
3 = Setpoint Analog/Digital
4 = External Alarm
Default: 1
P104 (H68)

Full scale of Analog Output 1 (Power Avarage) Kw R/W
Function: This parameter is used to adjust the full scale value of the analog output.
Min/Max: 0 ÷ 300.0 Kw for size from 25 to 300A
0 ÷ 3000 Kw for size upper to 300A
Default: 1000