CD Automation srl CD3000E-3PH from 25A to 500A User’s Manual
53
P011 (H0B)

Voltage supply V R
Function: This parameter read only contains the voltage value of the power supply.
P019 (H13)

Maximum output % R/W
Function: This parameter set in % the maximum output voltage.
Min/Max: 0 ÷ 100%
Default: 100
P024 (H18)

Setpoint Ramp Up Sec R/W
Function: This parameter set the Setpoint Ramp Up.
Min/Max: 0 ÷ 1000 seconds
Default: 2
P025 (H19)

Setpoint Ramp Down Sec R/W
Function: This parameter set the Setpoint Ramp Down.
Min/Max: 0 ÷ 1000 seconds
Default: 2
P031 (H1F)

Average voltage output on the three phases V R
Function: This parameter read only show the Average voltage output on the three phases.
P032 (H20)

Average power output on the three phases Kw R
Function: This parameter read only show the Average power output on the three phases.
P033 (H21)

RMS Current on the phase R A R
Function:
This parameter read only shows the RMS current present on the power terminal
L1.
P034 (H22)

RMS Current on the phase S A R
Function:
This parameter read only shows the RMS current present on the power terminal
L2.
P035 (H23)

RMS Current on the phase T A R
Function:
This parameter read only shows the RMS current present on the power terminal
L3.
P116 (H74)

Operative Load Voltage V R/W
Function: This parameter is used to set in volt the operative voltage of the load.
Min/Max: 24 ÷ 1000V
Default: 400 (if not specified in the Order Code)
Note: For voltage under the 330V or upper to 600V its necessary makes hardware
modification. For this reason it's very important specify this value in the Order
Code.
P119 (H77)

Load nominal Current A R/W
Function: This parameter is used to set the Load nominal Current.
Min/Max: 0 ÷ 300.0 Ampere for size from 25 to 300A
0 ÷ 3000 Ampere for size upper to 300A
Default: Max Current of CD3000E (if not specified in the Order Code)
Example: Size of CD3000E (Max Current) : 100A
Load nominal Current: 50A
P119  =50.0
Note: This parameter is necessary to have the correct rescaling inside the unit. For
this reason it's very important specify this value in the order code.