CD Automation srl CD3000E-3PH from 25A to 500A User’s Manual
53
P011 (H0B)
Voltage supply V R
Function: This parameter read only contains the voltage value of the power supply.
P019 (H13)
Maximum output % R/W
Function: This parameter set in % the maximum output voltage.
Min/Max: 0 ÷ 100%
Default: 100
P024 (H18)
Setpoint Ramp Up Sec R/W
Function: This parameter set the Setpoint Ramp Up.
Min/Max: 0 ÷ 1000 seconds
Default: 2
P025 (H19)
Setpoint Ramp Down Sec R/W
Function: This parameter set the Setpoint Ramp Down.
Min/Max: 0 ÷ 1000 seconds
Default: 2
P031 (H1F)
Average voltage output on the three phases V R
Function: This parameter read only show the Average voltage output on the three phases.
Average power output on the three phases Kw R
Function: This parameter read only show the Average power output on the three phases.
P033 (H21)
RMS Current on the phase R A R
Function:
This parameter read only shows the RMS current present on the power terminal
L1.
P034 (H22)
RMS Current on the phase S A R
Function:
This parameter read only shows the RMS current present on the power terminal
L2.
P035 (H23)
RMS Current on the phase T A R
Function:
This parameter read only shows the RMS current present on the power terminal
L3.
P116 (H74)
Operative Load Voltage V R/W
Function: This parameter is used to set in volt the operative voltage of the load.
Min/Max: 24 ÷ 1000V
Default: 400 (if not specified in the Order Code)
Note: For voltage under the 330V or upper to 600V its necessary makes hardware
modification. For this reason it's very important specify this value in the Order
Code.
P119 (H77)
Load nominal Current A R/W
Function: This parameter is used to set the Load nominal Current.
Min/Max: 0 ÷ 300.0 Ampere for size from 25 to 300A
0 ÷ 3000 Ampere for size upper to 300A
Default: Max Current of CD3000E (if not specified in the Order Code)
Example: Size of CD3000E (Max Current) : 100A
Load nominal Current: 50A
P119 =50.0
Note: This parameter is necessary to have the correct rescaling inside the unit. For
this reason it's very important specify this value in the order code.