12.4 Analog Outputs
The CD3000E thyristor unit have 1 analog output (0÷10V, 4÷20mA, ecc).
The output is for retransmitting the average power on the three phases.
12.4.1 Output 1: Average Power (Terminals 10 and 6 or 10 and 7)
The average power output is already configured in line with customer requirements that are defined in
the Order Code. The Order Code is written on the identification label.
However, if you wish to change the average power output (ex. from 0÷10V to 4÷20mA) proceed as
follows:
Caution: this procedure must be performed only by qualified persons
Size S09 Size S11/S13/S14
Setting the Output Value
The parameter P104 allows to set the full scale value to have the maximum output,
for example if you use an indicator with full scale 50Kw set the parameter P104 = 50.