CET Inc.
46
Register
Property
Description
Format
Range, Default*
6400
RW
Reserved
-
6401
RW
Unit ID
UINT16
1 to 247, 100*
6402
RW
Baud Rate
UINT16
0=1200, 1=2400, 2=4800,
3=9600*, 4=19200,
Others=Reserved
6403
RW
Comm. Config.
UINT16
0=8N2, 1=8O1, 2=8E1*
3=8N1, 4=8O2, 5=8E2
Table 5-27 Communication Setup
Notes:
1) If the Baud Rate is set to an invalid value, it will default to 9600bps automatically.
5.11 Data Recorder Setup (PMC-340B Only)
Register
Property
Description
Format
Range, Default*
6500
RW
Trigger Mode
UINT16
0=Disabled
1=Triggered by Timer*
6501
RW
Recording Mode
1
UINT16
0=Stop-when-Full
1=First-In-First-Out*
6502
RW
Recording Depth
1
UINT16
0 to 28,400*
6503
RW
Recording Interval
1
UINT32
1 to 3456000s, 600s*
6505
RW
Offset Time
2
UINT16
0* to 43200s
6506
RW
Number of Parameters
1
UINT16
0 to 16, 14*
6507
RW
Parameter #1
1,3
UINT16
100 (kWh Import)*
6508
RW
Parameter #2
1,3
UINT16
101 (kWh Export)*
6509
RW
Parameter #3
1,3
UINT16
104(kvarh Import)*
6510
RW
Parameter #4
1,3
UINT16
105 (kvarh Export)*
6511
RW
Parameter #5
1,3
UINT16
108 (kVAh)*
6512
RW
Parameter #6
1,3
UINT16
603 (kW Total Demand)*
6513
RW
Parameter #7
1,3
UINT16
604 (kvar Total Demand)*
6514
RW
Parameter #8
1,3
UINT16
605 (kVA Total Demand)*
6515
RW
Parameter #9
1,3
UINT16
600 (Ia Demand)*
6516
RW
Parameter #101
1,3
UINT16
601 (Ib Demand)*
6517
RW
Parameter #11
1,3
UINT16
602 (Ic Demand)*
6518
RW
Parameter #12
1,3
UINT16
109 (DI1 Pulse Counter)*
6519
RW
Parameter #13
1,3
UINT16
110 (DI2 Pulse Counter)*
6520
RW
Parameter #14
1,3
UINT16
111 (DI3 Pulse Counter)*
6521
RW
Parameter #15
1,3
UINT16
0 (Not Used)
6522
RW
Parameter #16
1,3
UINT16
0 (Not Used)
Table 5-28 Data Recorder Setup
Notes:
1) Changing any of these Data Recorder setup registers will reset the Data Recorder.
2) Recording Offset can be used to delay the recording by a fixed amount of time from the
Recording Interval. For example, if the Recording Interval is set to 3600 (hourly) and the
Recording Offset is set to 300 (5 minutes), the recording will take place at 5 minutes after the
hour every hour, i.e. 00:05, 01:05, 02:05…etc. The value of the Recording Offset parameter
should be less than the Recording Interval parameter.
3) Please refer to Appendix A for a complete list of Data Recorder Parameters.
5.12 TOU Setup
5.12.1 Basic
Register
Property
Description
Format
Range, Default*
7000
RO
Current Tariff
1
UINT16
0=T1, 1=T2
2=T3, 3=T4
7001
RO
Current Season
UINT16
0 to 11
(Season #1 to #12)

Table of Contents

Other manuals for CET PMC-340

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CET PMC-340 and is the answer not in the manual?

CET PMC-340 Specifications

General IconGeneral
BrandCET
ModelPMC-340
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals