3 Controller overview
3.1 Introduction of the controller
Chiller’s VariPro is a bus-based room controller designed for adjusting room
temperature. It is used to control GRAND VariPro, BOX VariPro and STUDIO
VariPro fan coils that are based on EC technology and equipped with a VariPro
control card.
The VariPro room controller has two RS-485 interfaces, and it can be connected
to any building management system based on the Modbus RTU protocol.
3.2 Operating principle of the controller
Using the VariPro room controller you can set the temperature of a room with 0,5
°C precision. The in-built temperature sensor of the controller continually
measures the temperature of a room with 0,1 °C precision. The required cooling
power control for the fan coil unit is calculated by the temperature differential
between the measured and set room temperatures. The method of control is PI
control. First, the power is increased by the amount calculated from the
differential (relative control P). After this, power increase continues
automatically, until the differential decreases (integrative part I). This means that
the temperature in the room is decreasing. When the set temperature is
reached, the relative control part P is reset. The accumulated integrative part I
stays as a constant while the room temperature is at the set temperature. If the
room temperature continues to decrease, the integrative part is decreased. If the
room temperature continues to increase, the integrative part is increased.
The functioning of the control algorithm aims to keep a balance where the
cooling power in the room and the heating load annul each other. Because of
different and variable heating loads, the balance is reached with different cooling
power levels even if the set temperature remains the same. In terms of the
control algorithm, changes in the set temperature and the heating load
correspond to each other. A change in either one starts the control, and a new
balance is sought. The same operating principle applies for the heating mode,
only the control directions are reversed.