26
| INSTALLATION MANUAL PRORAPID
switches on when an anti-legionella heating
starts. The relay switches o when the AL-
heating was completed successfully or if the
enable time for the AL-heating is exceeded.
Activate or deactivate function
Error Messages
The relay is switched on if one or several of
the set protective functions are activated.
This function can be inverted so that the
relay is turned on (Duration on) and then
turned o again if a protective function is
activated.
Error message
Activate or deactivate function
The additional function error message
activates the relay for certain events and
only deactivates again when the information
message to each event was read.
Sensor Calibration
Deviations in the temperature values
displayed, for example. due to cables
which are too long or sensors which are not
positioned optimally can be compensated
for manually here. The settings can be made
for each individual sensor in steps of 0.5 °C.
!
Settings are only necessary
in special cases at the time
of initial commissioning
by the specialist. Incorrect
measurement values can
lead to unpredictable errors.
Commissioning
Starting commissioning help guides you in
the correct order through the basic settings
necessary for commissioning, and provides
brief descriptions of each parameter in the
display. Pressing the ‚esc‘ key takes you
back to the previous value so you can look
at the selected setting again or adjust it
if desired. Pressing ‚esc‘ more than once
takes you back to the selection mode, thus
cancelling the commissioning help (See “
Commissioning help “ on page 10).
!
May only be started
by a specialist during
commissioning! Observe
the explanations for the
individual parameters in
these instructions, and
check whether further
settings are necessary for
your application..