| INSTALLATION MANUAL PRORAPID
the target temperature at the corresponding
storage sensor is reached, storage heating
is switched o. This should be factory set. If
not, select 2 degrees.
Complete loading
With the complete loading function,
the storage is heated up to the lower
storage sensor (S2). If complete loading is
deactivated, heating switches o when the
target storage temperature at the upper
storage sensor (S1) is reached. The storage
heating is always switched on via the
storage sensor S1. This should be factory
set. If not, select operation.
Heating times
Enable period for storage heating.
Heating times should be selected for
continuous operation only.
4. Protective Functions
The ‘Protective functions‘ can be used by
specialists to activate and set various pro-
tective functions.
Anti Legionella
With the help of the anti legionella function
(hereinafter referred to as: AL), the system
can be heated up at selected times in order
to free it of legionella.
By no means does the
controller replace the safety
appliances on site!
!
In the delivery state, the
anti legionella function is
switched o.
!
As soon as it has heated
up with “AL” turned on,
information with the date will
be shown in the display.
Exit protections
5.2 Seizing protection
5.1 Anti-legionella
OK