EasyManuals Logo

Circutor computer MAX 12 User Manual

Circutor computer MAX 12
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
12
computer MAX
Instruction Manual
it measures the total current of all the loads, including also the compensation capacitor bank
(see
Figure 3)
The CT should be installed preferably in phase L1, while the voltage measuring terminals of
ComputerMAXshouldbeconnectedtophasesL2andL3(seeschematicsin
Figure 4 and Fig-
ure 5
). It’s important to respect the connection senses of P1-P2 and S1-S2 shown in the above
mentionedgs,otherwisethephasedifferencewillhavetobecorrectedbyadjustingthedevice
according to set-up procedure indicated in “6.1.8.- U, I PHASE ANGLE SETTING.”.
RIGHT CONNECTION WRONG CONNECTION
The CT measures the whole
current of loads + capacitor
bank.
In case of malfunction check
that the CT is not shortcircuited
If CT is placed in this position,
NONE of the CAPACITOR STAGES
WILL CONNECT.
The equipment does not regulate
properly
If CT is placed in this position ALL
THE CAPACITOR STAGES WILL
CONNECT.
WARNING! This situation may
cause overcompensation, reso-
nance and overcurrent
Figure 3:Placement of current transformer (CT)
4.3.-CABLINGCROSSSECTIONSANDPROTECTIONS
The supply circuit must be protected by means of fuses or a circuit breaker sized between 0,5
and 2 A.
Recommendedfusesaregltype(IEC269)orMtype(IEC127).Amaincircuitbreakermustbe
providedinordertoallowthedisconnectionofcontrolcircuitsfromsupply(Computer,relays,
contactor coils, etc.)
The main switch must be easily accessible. The cabling cross section must be minimum 1,5
mm
2
for the voltage supply and for the relay outputs and 2,5 mm
2
for the cables connecting
secondary of CT to computer MAX. For distances between CT and computer higher than 10m
the cross section of the last must be increased at a rate of 1 extra mm
2
every 10 m.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Circutor computer MAX 12 and is the answer not in the manual?

Circutor computer MAX 12 Specifications

General IconGeneral
BrandCircutor
Modelcomputer MAX 12
CategoryController
LanguageEnglish

Related product manuals