Instruction Manual
CVM-C4
6.3.4.- ALARM VALUE
Note: Visible variable if the relay operating mode has been configured as an alarm output. Not visible
if the alarm parameter is the digital inputs (di-1, di-0, d2-1, d2-0).
The display value after which the alarm will be activated is configured on this screen.
do-1
uAL
0000
>3s
do-1
uAL
0000
.
.
VV
With a long keystroke (>3s), press to access the value's configuration.
When the desired value is shown on the screen, press the and keys to skip the digit.
When you reach the last digit and press the key, you select the position of the decimal point. Use
the key to modify the decimal point.
If you press again the key, the following units are selected: V, kV, MV
Minimum configuration value:
0.000 V, For alarm parameters: Un. H, Un. L, UL. H and UL. L
0.000 A, For alarm parameters: i. H and i. L
0.000 W, For alarm parameters: P. H and P. L
0.000 var, For alarm parameters: q. H and q. L
0.000 VA, For alarm parameters: s. H and s. L
-1.000, For alarm parameters: PF. H and PF. L
00.00 Hz, For alarm parameters: F. H and F. L
00.00%, For alarm parameters: UtH.H, UtH.L, itH.H and ith.L
Maximum configuration value:
9999 MV, For alarm parameters: Un. H, Un. L, UL. H and UL. L
9999 MA, For alarm parameters: i. H and i. L
9999 MW, For alarm parameters: P. H and P. L
9999 Mvar, For alarm parameters: q. H and q. L
9999 MVA, For alarm parameters: s. H and s. L
1.000, For alarm parameters: PF. H and PF. L
99.99 Hz, For alarm parameters: F. H and F. L
99.99%, For alarm parameters: UtH.H, UtH.L, itH.H and ith.L
With a long keystroke, press to validate the data.
Use the keys and to browse through the menu screens.