60
CVM-C4
Instruction Manual
8. TECHNICAL FEATURES
AC Power supply
(10)
Rated voltage
80... 270 V ~
Frequency 50 / 60 Hz
Consumption 6... 18 VA
Installation category CAT III 300V
DC Power supply
(10)
Rated voltage 80... 270 V 18... 36 V
Consumption 1.5 ...1.8 W 1,8... 2.2 W
Installation category CAT III 300V
(10)
Depending on model:
CVM-C4
Model
Power supply
80... 270 V ~ 80... 270 V 18... 36 V
M52706
-
M527060030000 - -
Voltage measurement circuit
Rated voltage (Un) 100 ... 277 V
Ph-N
~ ± 8 %
Frequency measuring margin 45... 65 Hz
Overvoltage 1.2 Un continuous, 2 Un Instantaneous (1 min)
Consumption < 0.2 VA (per phase)
Impedance > 1.7 MΩ
Installation category Cat III 300V
Current measurement circuit
Rated current (In) 1 A / 5 A ~
Frequency measuring margin 45... 65 Hz
Overcurrent 1.2 In continuous, 10 In Instantaneous (5s)
Consumption < 0.2 VA (per phase)
Impedance
< 20 mΩ
Installation category Cat III 300V
Accuracy
Voltage measurement 0.2 % ± 1 digit
Current measurement 0.2 % ± 1 digit
Frequency measurement 0.5 %
Active and reactive power measurement 0.5 % ± 2 digits
Active energy measurement Class 0.5s (IEC 62053-22)
Reactive energy measurement Class 2 (IEC 62053-23)
Relay outputs
Quantity 2
Contact capacity (resistive) AC: 5A / 250 V~ , DC: 5A / 30 V
Maximum voltage open contacts 277 V~ / 30 V
Maximum current 5 A
Maximum switching capacity 1385 VA / 150 W
Electrical life (250 V~ / 5A) 1 x 10
5