Unpacking and Installing the Cisco ONS 15454 Four-Shelf and Zero-Shelf Bay Assembly
78-13271-05
Fuse and Alarm Panel Wiring
Figure 22 FAP and power
The Cisco ONS 15454 bay assemblies use 4-pair, CAT 3-rated, twisted pair wire for FAP wiring. To
achieve all of the alarming capabilities of the FAP the wiring is doubled on the pins of the alarm cards.
Table 1 lists the FAP wiring for each wire pair and Figure 23 illustrates the FAP wiring.
Log on to http://www.cisco.com/techsupport or call the Cisco Technical Assistance Center (TAC) to
report a service-affecting problem (800 553-2447).
Table 1 FAP Power Alarm Wiring
59174
Wire Pair FAP Termination Environmental Termination
First pair: Loss of power
White/Blue (C)-Blue/White (NO)
1
Side: A1
Pin column: Power
Pins: 2 and 3
First environmental
termination at the bottom of
the 15454 shelf
Second pair: Loss of power
White/Orange (C)-Orange/White (NO)
2
Side: B1
Pin column: Power
Pins: 2 and 3
Second environmental
termination at the bottom of
the 15454 shelf
Third pair: Fuse
White/Green (C)-Green/White (NC)
3
Side: A
Pin column: Fuse
Pins: 4 and 5
Third environmental
termination at the bottom of
the 15454 shelf
Fourth pair: Fuse
White/Brown (C)-Brown/White (NC)
4
Side: B
Pin column: Fuse
Pins: 4 and 5
Fourth environmental
termination at the bottom of
the 15454 shelf
Fifth pair: Fuse
White/Slate (C)-Slate/White (NO)
5
Side: A2
Pin column: Power
Pins: 5 and 6
Fifth environmental
termination at the bottom of
the 15454 shelf
Sixth pair: Fuse
Red/Blue (C)-Blue/Red (NO)
6
Side: B2
Pin column: Power
Pins: 5 and 6
Sixth environmental
termination at the bottom of
the 15454 shelf
1. Place a jumper wire from side A1/power, pins 2 and 3 to use the first alarm for a loss of power to the A sides.
2. Place a jumper wire from side B1/power, pins 2 and 3 to use the second alarm for a loss of power to the B sides.
3. Place a jumper wire from side A/fuse, pins 4 and 5 to use the third alarm for a blown fuse condition on the
Asides.
4. Place a jumper wire from side B/fuse, pins 4 and 5 to use the fourth alarm for a blown fuse condition on the
Bsides.
5. Place a jumper wire from side A2/power, pins 5 and 6 to use the fifth alarm for a loss of power to the A2 sides.
6. Place a jumper wire from side B2/power, pins 5 and 6 to use the sixth alarm for a loss of power to the B2 sides.