5.3.2 ORIENTABLE BRACKET MOUNTED INSTALLATION
An alternative optional orientable wall-mounted or valve bracket for D35.
5.3.3 RECOMMENDED INSTALLATION
Depending on the cellular network signal strength, the D35 installation might need to be adapted. The network signal quality
values mentioned below are indicative and correspond to a signal acquired with a High-Performance Cellular Signal and
Network Analyzer, reference: Siretta® «SNYPER-LTE».
5.3.4 STRANDARD INSTALLATION
The standard installation of the D35 on the wall should be, as close as possible to the well opening, but not further than
1.5 m from the pressure sensor(s) connection(s) on the valve.
The minimum signal strength is - 80 dBm for optimum data communication at the valve level.