Blower Performance Data – TR Hybrid 015
Rated
CFM
Min CFM
Motor
Type
Motor Speed
Setting
External Static Pressure (in. wg)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
525 375
ECM -
Constant
Torque
1
RPM 838 902 974 1055 1126
Power (W) 83 90 96 103 110
CFM 589 549 505 452 393
2
RPM 935 996 1070 1146 1210 1266
Power (W) 107 110 118 126 132 137
CFM 618 561 517 460 411 371
3
RPM 1016 1081 1150 1233 1291 1338
Power (W) 125 132 141 149 155 159
CFM 615 576 529 471 428 386
4
RPM 1163 1241 1316 1365 1413
Power (W) 160 169 177 184 189
CFM 602 557 493 454 417
5
RPM 1252 1317 1391 1438
Power (W) 191 198 208 215
CFM 626 577 519 480
525 375
ECM -
Constant
Volume
Minimum CFM
RPM 723 793 813 934 1004 1074 1161
Power (W) 27 44 62 80 97 115 133
CFM 375 375 375 375 375 375 375
Default CFM
RPM 756 830 872 976 1049 1123 1207 1269 1343
Power (W) 53 76 99 121 143 166 189 211 234
CFM 525 525 525 525 525 525 525 525 525
Maximum CFM
RPM 777 851 924 1000 1078 1149 1221 1298 1372 1446
Power (W) 84 107 131 154 176 200 224 247 270 293
CFM 625 625 625 625 625 625 625 625 625 625
Interpolation is permissible; extrapolation is not.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
See performance correction tables for operating conditions other than those listed above.