Blower Performance Data – TR Hybrid 018
Rated
CFM
Min CFM
Motor
Type
Motor Speed
Setting
External Static Pressure (in. wg)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
600 450
ECM -
Constant
Torque
1
RPM 774 842 914 1002 1101
Power (W) 87 93 100 110 120
CFM 659 634 600 557 505
2
RPM 823 873 942 1017 1100 1209 1267 1318
Power (W) 104 110 118 127 136 149 155 161
CFM 707 691 658 622 580 515 464 426
3
RPM 866 905 975 1038 1111 1191 1299 1354 1397
Power (W) 124 129 138 146 156 166 180 188 192
CFM 754 749 715 685 648 608 542 496 456
4
RPM 1070 1133 1201 1277 1378 1443 1487
Power (W) 174 184 194 205 220 230 236
CFM 756 726 691 653 597 543 507
5
RPM 1288 1359 1442 1532
Power (W) 236 248 262 276
CFM 737 702 659 593
600 450
ECM -
Constant
Volume
Minimum CFM
RPM 682 772 860 950 1041 1128 1216 1306 1395 1484
Power (W) 46 69 93 115 136 161 185 207 230 253
CFM 450 450 450 450 450 450 450 450 450 450
Default CFM
RPM 752 829 904 982 1062 1136 1211 1289 1366 1442
Power (W) 75 99 122 145 167 191 215 238 261 284
CFM 600 600 600 600 600 600 600 600 600 600
Maximum CFM
RPM 831 902 967 1042 1123 1183 1248 1323 1394 1464
Power (W) 123 150 177 205 234 260 287 315 342 370
CFM 750 750 750 750 750 750 750 750 750 750
Interpolation is permissible; extrapolation is not.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
See performance correction tables for operating conditions other than those listed above.