8.11 PROBE POSITION
Fresh air probe
A
A
8 - MAINTENANCE
8.10 AIR COIL
Contact with the exchanger fins can cause cuts. Wear
protective gloves to perform the above described operations.
It is extremely important that the battery gives the maximum
thermal exchange; therefore, its surface must be cleaned from
dust and deposits. Remove all impurities from the surface.
It is extremely important that the battery gives the maximum
thermal exchange; therefore, its surface must be cleaned from
dust and deposits. Remove all impurities from the surface.
Using an air pressure gun, clean the aluminum surface of the
battery. Be careful to direct the air in the opposite direction of
the fan air movement.
Hold the gun parallel to the fins to avoid damages. As an
alternative, an aspirator can be used to suck impurities from
the air input side.
Verify that the aluminum fins are not bent or damaged. In the
event of damages, contact the authorized assistance center
and get the battery “ironed out” in order to restore the initial
condition for an optimal air flow