31
7 - CONTROL
The scheduling can be programmed for each day of the week.
Parameter :
AS20 antilegionella set-point
AS04 DHW hysteresis
ANTILEGIONELLA SCHEDULING
Day Cycle duration
(0= OFF
from 1 to 24
hours)
Hours Minutes
Monday
AS25 = 0 AS26 AS27
Tuesday
AS28 = 0 AS29 AS30
Wednesday
AS31 = 1 AS32 = 23 AS33 = 00
Thursday
AS34 = 0 AS35 AS36
Friday
AS37 = 0 AS38 AS39
Saturday
AS40 = 0 AS41 AS42
Sunday
AS43 = 2 AS44 = 22 AS45= 30
In the following example the antilegionella cycle is scheduled:
Wednesday duration 1 starting at 23:00
Sunday duration 2 starting at 22:30
7.4 DOMESTIC HOT WATER
To enable the DHW function:
Par AS00 DHW operating
1 = Enable the heat pump for DHW + DHW 3-way
valve
3 = Enable the heat pump for DHW + electric
heater + DHW 3-way valve
Parameters to setting :
Main menu
Parameters
AS
AS00
Parameter modification
DHW SCHEDULING
To enable the hour scheduling:
Par tE00 hour scheduling
0 = disabled
1 = enabled
Main menu
Parameters
tE
tE00
Parameter modification
Main menu
Parameters
AS
AS20
Parameter modification
Parameter :
AS01 DHW setpoint
AS04 DHW hysteresis
CL90 = 9
CE00 = 2
CE30 = 11
CE50 = 0
CE90 = 28
AS00 = 1
AS04 = 5
AS05 = 5
AS06 = 20