28 WSAT-XIN 21-171 M0Q940G14-03
7.16 Antifreeze function with circulating pump
Parameter modication Keys Esc + Set Menu dS Menu PI
PI51 switch-on setpoint of the circulating pump for antifreeze (5°C)
PI52 hysteresis (2°C)
The function is enabled by default
To deactivate the funcion: PI50 = 0.
pump
Off
Pi52
ON
Pi51
t H
2
O inlet
7.17 Start-up report
Identifying the operating objective conditions is useful to control the unit over time.
With unit at steady state, i.e. in stable and close-to-work conditions, identify the following data:
total voltages and absorptions with unit at full load
absorptions of the dierent electric loads (compressors, fans, pumps etc)
temperatures and ows of the dierent uids (water, air) both in input and in output from the unit
temperature and pressures on the characteristic points of the refrigerating circuit (compressor discharge, liquid, intake)
The measurements must be kept and made available during maintenance interventions.
7.18 2014/68/UE PED directive
DIRECTIVE 2014/68/UE PED gives instructions for installers, users and maintenance technicians as well.
Refer to local regulations; briey and as an example, see the following:
Compulsory verication of the rst installation:
only for units assembled on the installer’s building site (for ex. Condensing circuit + direct expansion unit)
Certication of setting in service:
for all the units
Periodical verications:
to be executed with the frequency indicated by the Manufacturer (see the “maintenance inspections” paragraph)