TN836 High Current Digital Series AC to DC Power Supplies
MT-3/4 Radio Systems
TECHNICAL NOTES
Page 3 of 4
LMRSALES@CODANCOMMS.COM
CODANCOMMS.COMTECHNICAL NOTE:
TN836, REV 3-0-0, © Aug 2016
CANADA/US +1 250 382 8268 | TOLL FREE +1 800 664 4066
Remote Control and Alarm Connector
A REMOTE connector on the back panel of the power supply allows for the following functionality:
Pin Number Pin Description Functionality
Pin 1 REM SD+ Remote shutdown control lines (TTL compatible)
Pin 2 REM SD- Hi = output off ; Low = output on
Pin 3 REM SNS+ Remote voltage sense lines for tighter voltage regulation at load
Pin 4 REM SNS- Default sense point is at busbars
Pin 5 Common Alarm Output Common
Pin 6 NO Alarm Output Normally Open contact (0.5 A 125 Vac max.)
Pin 7 NC Alarm Output Normally Closed contact (0.5 A 125 Vac max.)
Alarms
Alarm Output activation setting is enabled or disabled through the TCP/IP web based utility (for units without the
Ethernet option the form C relay output will always be activated for an alarm condition). Available alarms are as
follows:
DC Output Voltage Failure Alarm Output voltage rises above ≈ 110% of the maximum rated output.
Alarm latches output off , clears when DC output manually re-enabled.
DC Overcurrent Shutdown Alarm Output current rises above ≈ 115% of the maximum rated output.
Alarm latches output off , clears when DC output manually re-enabled.
AC Input Voltage Failure Alarm AC Input voltage falls below ≈ 90 Vac.
Alarm latches output off , automatically clears when AC input rises .
above ≈ 100 Vac for 3 seconds.
System Failure Alarm Internal system failure.
Alarm latches output off , clears when DC output manually re-enabled.
and internal fault is no longer present.
Over-Temperature Alarm Internal over-temperature limit exceeded.
Alarm latches output off , automatically clears when temperature .
returns to normal operating range.
Parallel Unit Offl ine Alarm Communication is lost between parallel units.
Output state unaff ected. No eff ect if parallel operation is not active.