This setpoint adjusts the "deadband" for the running hours equalization function.
The priorities are swapped not until the relative engine hours (RHE) difference is
higher than this deadband.
Setpoint: #PwrBandContr 1
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
This setpoint is used to select the gen-sets which will run within the power band
#1 if the optimalization according to gen-set size is active. Learn more about this
topis in the chapter Gen-set size optimalization.
NOTE:
The combinations of gensets must be created so, that the total nominal power of
the Power band #1 < #2 < #3 < #4.
Setpoint: #PwrBandContr 2
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
This setpoint is used to select the gen-sets which will run within the power band
#2 if the optimalization according to gen-set size is active. Learn more about this
topis in the chapter Gen-set size optimalization.
NOTE:
The combinations of gensets must be created so, that the total nominal power of
the Power band #1 < #2 < #3 < #4.
Setpoint: #PwrBandContr 3
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
This setpoint is used to select the gen-sets which will run within the power band
#3 if the optimalization according to gen-set size is active. Learn more about this
topis in the chapter Gen-set size optimalization.
NOTE:
The combinations of gensets must be created so, that the total nominal power of
the Power band #1 < #2 < #3 < #4.