EasyManua.ls Logo

ComAp IG-NTC GC

ComAp IG-NTC GC
260 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IGS-NT-BC, SW Version 1.2.0, ©ComAp January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
119
Setpoint: #RunHrsMaxDiff
Group
Pwr management
Range [units]
0 .. 65000 [h]
Related FW
3.0
Description
This setpoint adjusts the "deadband" for the running hours equalization function.
The priorities are swapped not until the relative engine hours (RHE) difference is
higher than this deadband.
Setpoint: #PwrBandContr 1
Group
Pwr management
Range [units]
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
Related FW
3.0
Description
This setpoint is used to select the gen-sets which will run within the power band
#1 if the optimalization according to gen-set size is active. Learn more about this
topis in the chapter Gen-set size optimalization.
NOTE:
The combinations of gensets must be created so, that the total nominal power of
the Power band #1 < #2 < #3 < #4.
Setpoint: #PwrBandContr 2
Group
Pwr management
Range [units]
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
Related FW
3.0
Description
This setpoint is used to select the gen-sets which will run within the power band
#2 if the optimalization according to gen-set size is active. Learn more about this
topis in the chapter Gen-set size optimalization.
NOTE:
The combinations of gensets must be created so, that the total nominal power of
the Power band #1 < #2 < #3 < #4.
Setpoint: #PwrBandContr 3
Group
Pwr management
Range [units]
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
Related FW
3.0
Description
This setpoint is used to select the gen-sets which will run within the power band
#3 if the optimalization according to gen-set size is active. Learn more about this
topis in the chapter Gen-set size optimalization.
NOTE:
The combinations of gensets must be created so, that the total nominal power of
the Power band #1 < #2 < #3 < #4.

Table of Contents