IGS-NT-BC, SW Version 1.2.0, ©ComAp January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
118
power dropped below this minimal value.
There are 3 different MinRunPower setpoints, this particular one is activated by
the input MinRun power 1.
NOTE:
If more than one binary input for MinRunPower activation is closed MinRunPower
with higher number is used (i.e. binary inputs with higher number have higher
priority).
When no binary input is closed, then minimal running power is 0.
Setpoint: #MinRunPower 2
Group
Power Management
Range [units]
0 .. 65000 [kW]
Related FW
3.0
Description
This setpoint is used to adjust certain minimum value of the sum of nominal power
of all running gen-sets. If the function is active, then the gen-sets would not be
stopped, although the reserve for stop is fulfiled, if the total remaining nominal
power dropped below this minimal value.
There are 3 different MinRunPower setpoints, this particular one is activated by
the input MinRun power 2.
NOTE:
If more than one binary input for MinRunPower activation is closed MinRunPower
with higher number is used (i.e. binary inputs with higher number have higher
priority).
When no binary input is closed, then minimal running power is 0.
Setpoint: #MinRunPower 3
Group
Power Management
Range [units]
0 .. 65000 [kW]
Related FW
3.0
Description
This setpoint is used to adjust certain minimum value of the sum of nominal power
of all running gen-sets. If the function is active, then the gen-sets would not be
stopped, although the reserve for stop is fulfiled, if the total remaining nominal
power dropped below this minimal value.
There are 3 different MinRunPower setpoints, this particular one is activated by
the input MinRun power 3.
NOTE:
If more than one binary input for MinRunPower activation is closed MinRunPower
with higher number is used (i.e. binary inputs with higher number have higher
priority).
When no binary input is closed, then minimal running power is 0.