IGS-NT-BC, SW Version 1.2.0, ©ComAp January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
182
Value: Service time 4
Group
Statistics
Units
h
Related FW
3.0
Description
This is maintenance countdown timer #4. The timer is located in setpoints (group
Engine protect) as well as in values (group Statistics). Adjust the timer to the
requested maintenance interval. It will be then decremented while the gen-set is
running. The alarm WrnServiceTime is issued as soon as the timer counts down
to zero.
Value: TotalDownTime
Group
Statistics
Units
h
Related FW
3.0
Description
This counter counts while the controller is in "not ready" state, i.e. it can not be
started. The reason of the "not ready" state may be either some 2
nd
level alarm or
the controller switched in OFF mode.
NOTE:
The counter can be readjusted/reset from InteliMonitor menu Monitor -> Set
statistics.
Value: DnTimeReqToRun
Group
Statistics
Units
h
Related FW
3.0
Description
This counter counts while the controller is in "not ready" state (see the value Total
downtime) and there is a request for the gen-set to run.
NOTE:
The counter can be readjusted/reset from InteliMonitor menu Monitor -> Set
statistics.
Value: PulseCounter 1
Group
Statistics
Units
-
Related FW
3.0
Description
This is the value of PulseCounter #1 module. See the binary input PulseCounter
1.