IGS-NT-BC, SW Version 1.2.0, ©ComAp January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
188
manual is active:
Starter
Fuel solenoid
Prestart
Cooling pump
CB close/open (GCB and MCB)
CB ON coil (GCB and MCB)
CB OFF coil (GCB and MCB)
CB UV coil (GCB and MCB)
Stop solenoid
Stop pulse
Speed up
Speed dn
AVR up
AVR dn
Ignition
Ventilation
Idle/Nominal
Prelubr pump
In synchronism
ECU PwrRelay
Ready for load
Stand-by ready
Operational
Ready
Not Ready
CranckProcedure
Starting
Idle run
Running
ForwardSynchro
ReverseSynchro
Warming
Soft load
Loaded
Soft unld
Cooling
Stopping
Crancking
PeakShaveAct
Binary input: ManualLdRecon
Related FW
3.0
Description
This input is used for manual reconnection of the last disconnected part of the
load, if the load has dropped below the setpoint Ld recon level.
This input works only if automatic reconnection is disabled, i.e. the setpoint
AutoLd recon is set to DISABLED.
Binary input: FaultResButton
Related FW
3.0
Description
This input is used for an external FAULT RESET button mounted on the
switchboard. The function of the input is identical as function of the fault reset