Configuring of the reset input does not block writing the ExtValue remotely, in
comparison to the up and down inputs, which does. However, if the reset input is
active, the remotely written data are not accepted.
Binary input: ExtValue4reset
Related FW
3.0
Description
The ExtValue 4 is reset to it's default value when this input is activated and held
there until the input is deactivated. The default value is given by the setpoint
ExtValue4deflt.
While the reset input is active:
The value does not respond to up and down inputs.
The value does not accept new data that are written remotely from a
remote terminal using the ExtValue command.
NOTE:
Configuring of the reset input does not block writing the ExtValue remotely, in
comparison to the up and down inputs, which does. However, if the reset input is
active, the remotely written data are not accepted.
Binary input: IssueActCallC1
Related FW
3.0
Description
This input forces the controller to issue an active call/e-mail/SMS via the channel
#1. Type of the channel is to be adjusted by the setpoint AcallCH1-Type.
This input can be used to inform a remote user about a specific non-alarm
situation, e.g. mains failure and/or mains return:
1. Select a binary signal in the controller, which indicates, that the particular
situation occured, about which you want to be informed remotely. There
are many predefined binary informations provided directly by the
controller or use PLC functions to create the desired binary signal.
2. Configure an universal protection block to the binary signal mentioned
above and select protection type AL indication.
3. Configure the binary signal mentioned above onto the logical binary input
IssueActCallC1.
Binary input: IssueActCallC2
Related FW
3.0
Description
This input forces the controller to issue an active call/e-mail/SMS via the channel
#2. Type of the channel is to be adjusted by the setpoint AcallCH2-Type.
This input can be used to inform a remote user about a specific non-alarm
situation, e.g. mains failure and/or mains return:
1. Select a binary signal in the controller, which indicates, that the particular
situation occured, about which you want to be informed remotely. There