IGS-NT-BC, SW Version 1.2.0, ©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
The output is closed while there is at least one alarm of the Shutdown type
present in the alarm list. The alarm can be in any state, i.e. active unconfirmed,
active confirmed or inactive unconfirmed. See the chapter Alarm management for
more information.
Binary output: Common SdOvr
Common output that closes with 2s delay if any Shutdown override-type protection
becomes active. If it is already active and another protection of that type becomes
active, the output is deactivated for 2 seconds and then reactivated again to
inform on this new alarm.
Binary output: Common Stp
The output is closed while there is at least one alarm of the Slow stop type
present in the alarm list. The alarm can be in any state, i.e. active unconfirmed,
active confirmed or inactive unconfirmed. See the chapter Alarm management for
more information.
Binary output: Common Fls
The output is closed while there is at least one alarm of the Sensor fail type
present in the alarm list. The alarm can be in any state, i.e. active unconfirmed,
active confirmed or inactive unconfirmed.See the chapter Alarm management for
more information.
Binary output: Common LoP
This IS-NT specific function!
The output is closed while there is at least one alarm of the Low power type
present in the alarm list. See the chapter Alarm management for more
information.
Binary output: Common OfL
The output is closed while there is at least one alarm of the Off load type present
in the alarm list. See the chapter Alarm management for more information.