IGS-NT-BC, SW Version 1.2.0, ©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
The output is closed while the actual reserve is above the reserve for start from
the reserve set #3.
Binary output: Syst res 4 OK
The output is closed while the actual reserve is above the reserve for start from
the reserve set #4.
Binary output: AllAvailGS run
The output is closed while all gen-sets in the group, which participate in the power
management, are running and loaded.
The output is closed while the generator over/under voltage alarm is present in the
alarm list.
The output is closed while the bus over/under voltage alarm is present in the
alarm list.
Binary output: Overcurrent
The output is closed while there is either the Generator IDMT Overcurrent or
Generator Short current alarms present in the alarm list.
Binary output: Common Wrn
The output is closed while there is at least one alarm of the Warning type present
in the alarm list. The alarm can be in any state, i.e. active unconfirmed, active
confirmed or inactive unconfirmed. See the chapter Alarm management for more
information.