Description
The output is closed while the gen-set is loaded and the load is beeing regulated
according to selected mode (baseload, import/export, power management etc.) or
is not beeing regulated in single island operation.
Binary output: Logical 0
Related FW
3.0
Description
This output is always opened. It may be used in functions (e.g. ECU outputs or
PLC modules inputs) where a binary value is required, however it has to be
continously inactive.
Binary output: Logical 1
Related FW
3.0
Description
This output is always closed. It may be used in functions (e.g. ECU outputs or
PLC modules inputs) where continuously active binary value is required.
Binary output: Bin selector 1
Related FW
3.0
Description
Output is closed or opened according to the setpoint Bin selector 1.
NOTE:
The output is intended for ECU-controlled engines to switch on/off some particular
ECU function by a controller setpoint if the function can be controlled by a binary
value over the J1939 bus.
Binary output: Bin selector 2
Related FW
3.0
Description
Output is closed or opened according to the setpoint Bin selector 2.
NOTE:
The output is intended for ECU-controlled engines to switch on/off some particular
ECU function by a controller setpoint if the function can be controlled by a binary
value over the J1939 bus.
Binary output: Bin selector 3
Related FW
3.0
Description
Output is closed or opened according to the setpoint Bin selector 3.
NOTE:
The output is intended for ECU-controlled engines to switch on/off some particular
ECU function by a controller setpoint if the function can be controlled by a binary
value over the J1939 bus.