IGS-NT-BC, SW Version 1.2.0, ©ComAp January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
95
Setpoint: SHxOcol detect
Group
Comms settings
Range [units]
DISABLED, ENABLED [-]
Related FW
3.0
Description
This setpoint is used to enable/disable evaluation of collisions of virtual shared
peripherial modules. A collision means that there is more than one source (shared
outputs module) active on the CAN2 bus.
NOTE:
In certain situations multiple sites with bus tie breakers may need to have more
shared outputs sources as the CAN bus line is in some points interrupted
according to bus tie breakers position. Normally a collision would be indicated if
there were more sources on the bus and this setpoint can be used to disable the
evaluation of collisions in this special case.
Group: ComProtSettings
Setpoint: Bin selector 1
Group
Engine params
Range [units]
OFF, ON [-]
Related FW
3.0
Force value
possible
YES
Description
The setpoint is used to switch on and off the output Bin selector 1.
Setpoint: Bin selector 2
Group
Engine params
Range [units]
OFF, ON [-]
Related FW
3.0
Force value
possible
YES
Description
The setpoint is used to switch on and off the output Bin selector 2.
Setpoint: Bin selector 3
Group
Engine params
Range [units]
OFF, ON [-]
Related FW
3.0
Force value
possible
YES
Description
The setpoint is used to switch on and off the output Bin selector 3.