Alarm output: WrongConfig
This output is closed while there is the WrongConfig alarm present in the alarm
list. The wrong configuration is indicated if the controller configuration contains a
PLC program, which exceeds limits of the current controller hardware. Typically
this situation can occur when a miniCHP archive is used in a controller without
mCHP dongle inserted.
Alarm output: Dongle incomp
This output is closed while there is the Dongle incomp alarm present in the alarm
list. The incompatible dongle is indicated when a function is switched on, which
requires dongle, however the dongle is not inserted or does not contain the
appropriate feature.
Typical situations are:
• Power management is enabled and there is not any dongle with "PMS"
feature inserted in the controller.
• The controller is in situation, when the load sharing should beeing
performed, however there is not any dongle with "LS" feature inserted in
the controller.
Alarm output: Emergency stop
This output is closed while the Emergency stop alarm is present in the alarm list.
The emergency stop alarm is activated by the input Emergency stop.
Alarm output: WrnServiceT1+2
This output is closed while the WrnServiceT1+2 alarm is present in the alarm list.
This alarm occurs when the counter Service time 1 or Service time 2 has reached
zero value. Both timers must be reset to a nonzero value to get rid of this alarm.
Alarm output: WrnServiceT3+4
This output is closed while the WrnServiceT3+4 alarm is present in the alarm list.
This alarm occurs when the counter Service time 3 or Service time 4 has reached
zero value. Both timers must be reset to a nonzero value to get rid of this alarm.