InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
149
Related FW
3.0
Force value
possible
YES
Description
This setpoint determines treshold for busR overvoltage protection. This
protection is evaluated with delay given by setpoint BusRight V del.
Protection type is history record.
NOTE:
All three phases are checked for busR voltage detection. Maximum out of
those three is used.
For high voltage applications, the BusRNomVph-ph can be used for nominal
voltage setting.
12.2.7.3 Setpoint: BusRight <V
Group
BusR protect
Range [units]
50 .. BusRight >V [%]
Related FW
3.0
Force value
possible
YES
Description
This setpoint determines treshold for busR undervoltage protection. This
protection is evaluated with delay given by setpoint BusRight V del.
Protection type is history record.
NOTE:
All three phases are checked for busR voltage detection. Minimum out of
those three is used.
For high voltage applications, the BusRNomVph-ph can be used for nominal
voltage setting.
12.2.7.4 Setpoint: BusRight V del
Group
BusR protect
Range [units]
0.00 .. 600.00 [s]
Related FW
3.0
Description
This setpoint adjusts delay for busR under- (BusRight <V) and overvoltage
(BusRight >V) protections.