ECU SpeedAdj [ % ]
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50%.
Step: 1%
Range: 0 100%
Hint:
The minimum value 0% is equal to 90% of nominal speed. Maximum value 100% is equal to 110% of
nominal speed.
Fuel Pump ON [%]
When the actual value of Fuel Level is lower or equals to this value then the binary output Fuel Pump
is activated.
Step: 1
Range: 0 100 %
Fuel Pump OFF [%]
When the actual value of Fuel Level is higher or equals to this value then the binary output Fuel Pump
is deactivated.
Step: 1
Range: 0 100 %
Hint:
The two setpoints above are compared to Analog Input 3 (usually used for Fuel Level)
It is a prerequisite for this function to use a fuel level sensor at this analog input.
TempSwitch ON [-]
Threshold level for switching on the binary output TempSwitch. This function is connected with
controller's analog input 2.
Step: 1
Range: -100 .. 10000 [-]
TempSwitchOFF [-]
Threshold level for switching off the binary output TempSwitch. This function is connected with
controller's analog input 2.
Step: 1
Range: -100 .. 10000 [-]
Hint:
The description of Power Switch function is in chapter Binary outputs - list at Temp Switch.
PowerSwitch ON [kW]
Threshold level for switching the binary output “Power Switch” on.
Step: 1
Range: 0 32000 kW
PowerSwitchOFF [kW]
Threshold level for switching the binary output “Power Switch” off.
Step: 1
Range: 0 32000 kW
Hint:
The description of Power Switch function is in chapter Binary outputs - list at Power Switch.
FuelTankVolume [l]
Define a capacity of Genset fuel tank.
Step: 1
Range: 1 10000l

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp intelilite nt amf25 and is the answer not in the manual?

ComAp intelilite nt amf25 Specifications

General IconGeneral
Communication PortsRS232, RS485, USB
Power Supply8-36 VDC
Number of Digital Inputs8
Number of Digital Outputs8
Number of Analog Inputs3
Number of Analog Outputs2
DisplayLCD with backlight
Supported ProtocolsModbus
Operating Temperature-20°C to +70°C
Humidity95% non-condensing
Weight0.4 kg
ProtectionIP65 (front panel)
Controller TypeAMF Controller
Storage Temperature-30 to +80 °C