Deactivates in the moment when the measured values are back in limits. Fault reset has no effect on 
this output. 
I Unb Sig 
Signalling of current unbalance according to the setting in I Unb group. Activates immediately in the 
moment of fault conditions (does not wait until delay times out). Deactivates in the moment when the 
measured values are back in limits. Fault reset has no effect on this output. 
DOC Sig 
Signalling of directional overcurrent protection. Activates immediately in the moment of fault conditions 
(does not wait until delay times out). Deactivates in the moment when the measured values are back 
in limits. Fault reset has no effect on this output. 
DOC Test 
Test output for directional overcurrent protection. When the setpoint DOC Test is set to ENABLED, the 
directional overcurrent protection activates this output even if standard activating conditions are not 
fulfilled. This is to allow full quadrant range test of this protection – this output stays active all the time 
the protection senses the corresponding quadrant and magnitude of the current. Activating DOC test 
does blocks the regular function of the ANSI 67 directional overcurrent protection stage! 
EFC >Sig 
Signalling of earth fault over current condition according the setting in EFC group. Activates 
immediately in the moment of fault conditions (does not wait until delay times out). Deactivates in the 
moment when the measured values are back in limits. Fault reset has no effect on this output. 
IGS > Sig 
Signalling of ground surge protection according the setting in IGS group. Activates immediately in the 
moment of fault conditions (does not wait until delay times out). Deactivates in the moment when the 
measured values are back in limits. Fault reset has no effect on this output. 
NVD Sig 
Signalling of neutral voltage displacement conditions according the setting in NVD group. Activates 
immediately in the moment of fault conditions (does not wait until delay times out). Deactivates in the 
moment when the measured values are back in limits. Fault reset has no effect on this output. 
P Sig 
Signalling of out off limit power according the setting in P<> group. Activates immediately in the 
moment of fault conditions (does not wait until delay times out). Deactivates in the moment when the 
measured values are back in limits. Fault reset has no effect on this output. 
Sync Check 
Binary output related to ANSI 25 Synchro check. The output is active in either of the following cases: 
-  voltage, frequency and phase condition are met and dwell time is over according to the setting 
in Sync Check group 
-  connection to dead line or bus are enabled and the voltage is under Dead Voltage limit for the 
dwell time 
AC Reclosing 
Binary output related to ANSI 79 AC Reclosing. The output closes AR Delay after power-up of the unit. 
The output opens immediately when the appropriate trip event appears. The trip, which is considered 
for the reclosing function is selected by the setpoint AC Reclosing: Rec Initiate. The output closes 
again with the pre-set delay after the trip state terminates.