EasyManuals Logo

ComAp InteliPro User Manual

ComAp InteliPro
105 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #79 background imageLoading...
Page #79 background image
InteliPro, SW version 1.4, ©ComAp April 2014
InteliPro 1.4 Comprehensive Guide - rev. 1
4-23
V <>
V>, V>>, V<, V<< [V]
Threshold of 1st and 2nd stage overvoltage and 1st and 2nd stage undervoltage protection
respectively.
Step: 1 V
Range: 1 - 34000 V
0 = OFF, the appropriate stage of voltage protection is disabled
Default setting:
V> 253 V
V>> 265 V
V< 200 V
V<< 184 V
V> Del, V>> Del, V< Del, V<< Del [s]
Delay of the appropriate stage of the voltage protection.
Step: 0,01 s
Range: 0,00 - 600,00 s
Default setting:
V> Del 1,00 s
V>> Del 0,50 s
V< Del 2,50 s
V<< Del 0,50 s
Rst V [+/- 0% V<> , +/- 4% V<>, 95%NomVol]
Threshold for voltage measurement hysteresis.
Options:
+/- 0% V<>: no voltage hysteresis is applied
+/- 4% V<>: increase/decrease of the undervoltage/overvoltage limit by 4% of the limit
value
95%NomVol> reset value set to 95 % of the nominal voltage
Default setting: +/- 0% V<>
Avg V > [V]
Treshold of the 10 minutes floating average overvoltage
Step: 1 V
Range: 0 - 34000 V
0 - protection is disabled
Default setting: 253 V
V Trp BO [Trp 1 / Trp 2 / Trp 1+2 / None]
Selection of trip binary output for voltage protections.
Default setting: None

Table of Contents

Other manuals for ComAp InteliPro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliPro and is the answer not in the manual?

ComAp InteliPro Specifications

General IconGeneral
BrandComAp
ModelInteliPro
CategoryRelays
LanguageEnglish

Related product manuals