InteliSys
NT
-AFR-Abstract, SW version 1.0, ©ComAp – December 2006 33
IS-NT-AFR-1.0-Abstract.pdf
MisfMAP reduct [ Bar ]
Required MAP value is immediately reduced by this value when binary input Misfiring is active.
Step: 0,001 Bar
Range: -1,000 to 1,000 Bar
MisfLdRed del [ s ]
The engine load is reduced after MisfLdRed del when binary input Misfiring is activated.
Step: 1 s
Range: 0 to Misfiring del s
Misfiring del [ s ]
Engine cool down protection is activated when binary input Misfiring is activated for Misfiring del.
Step: 1 s
Range: MisfLdRed del to 600 s
Knocking del [ s ]
Engine shut down protection is activated when binary input DxLdReduct is activated for Knocking del.
Step: 1 s
Range: 0 to 600 s
MAP difference [ Bar ]
Allowed ± difference from MAP characteristic (Low MAP, High MAP).
Step: 0,001 Bar
Range: 0,000 to 1,000 Bar
MAP timeout [ s ]
Engine shut down is activated when actual MAP is out of characteristics (MAP difference) for MAP
timeout.
Step: 1 s
Range: 0 to 600 s
kWh pulse [ kWh ]
Number of kWh per one 1 sec pulse on Logical binary output “kWh pulse”. Pulse calculation starts
from setpoint change.
Step: 1 kWh
Range: 0 to 65535 kWh